APPENDIX B — H-100 GENERAL I/O AND CONNECTOR INFORMATION
H-100 ANALOG INPUTS
  Number 
Default Signal Name 
Default Signal Name 
Type 
Connector Pin
 
OIL TEMP 
Oil Temperature 
4-20 ma  
J1-9 source, 
  
 
 
 
J1-8 
return
 
COOLANT TEMP 
Coolant Temperature 
4-20 ma 
J1-15 source, 
  
 
 
 
J1-31 
return
 
OIL PRESSURE 
Oil Pressure 
4-20 ma  
J1-20 source, 
  
 
 
 
J1-19 
return
 
COOLANT LEVEL 
Coolant Level 
4-20 ma  
J1-30 source, 
  
 
 
 
J1-29 
return
 
USER CFG 05 
Analog Input #5 
4-20 ma 
J1-7 source, 
 
 
FUEL LEVEL 
Fuel Level 
 
J1-6 return
 
USER CFG 06 
Analog Input #6 
4-20 ma  
J1-28 source, 
 
 
FUEL PRESSURE 
Fuel Pressure, 
 
J1-27 return
  
INLET 
TEMP 
Inlet 
Temperature
 
USER CFG 07 
Analog Input #7 
4-20 ma 
J1-18 source,
 
 
THROT POS 
Throttle Position 
 
J1-17 return
 
USER CFG 08 
Analog Input #8 
0-1 Volt 
J1-5 source,
 
 
EMISSIONS 
Emissions Sensor, 
 
J1-5 return
 
 
FLUID BASIN 
Fluid Basin Level
 
USER CFG 09 
Analog Input #9 
0-10 Volt 
J1-16 return
 
 
BAT CHARGE CUR 
Battery Charge Current
 
10 
BATTERY VOLTS 
Battery Voltage 
0-30 Volt 
J1-35 ( + )
 
 
 
 
 
J1-12 ( - )
 
11 
CURRENT PHS A 
Phase A Current – single & three phase 
0-3 ARMS 
J2-12 ( + )
 
 
 
 
 
J2-11 ( - )
 
12 
CURRENT PHS B 
Phase B Current – single & three phase 
0-3 ARMS 
J2-35 ( + )
 
 
 
 
 
J2-34 ( - )
 
13 
CURRENT PHS C 
Phase C Current – three phase 
0-3 ARMS 
J2-10 ( + )
 
 
 
 
 
J2-9 ( - )
 
 
CURRENT NEUTRAL 
Current in Neutral – single phase 
Derived 
n/a
 
14 
AVRG CURRENT 
Average System Current 
Derived 
n/a
 
15 
VOLT PHS A-B 
Line-to-Line AB Voltage – three phase 
0-28.8 VRMS 
J2-6
 
 
VOLT PHS A-N 
Line-to-Neutral AN Voltage – single
 
16 
VOLT PHS B-C 
Line-to-Line BC Voltage – three phase 
0-28.8 VRMS 
J2-29
 
 
VOLT PHS B-N 
Line-to-Neutral BN Voltage – single
 
17 
VOLT PHS C-A 
Line-to-Line CA Voltage – three phase 
0-28.8 VRMS 
J2-17
 
 
VOLT PHS A-B 
Line-to-Line AB Voltage – single phase 
Derived 
n/a
 
18 
AVRG VOLTAGE 
Average Line-to-Line System Voltage 
Derived 
n/a
 
19 
TOTAL POWER KW 
Total System Real Power 
Derived 
n/a
 
20 
TOTAL PF 
Total System Power Factor 
Derived 
n/a
 
21 
GEN FREQUENCY 
Generator Frequency 
Derived 
n/a
 
22 
ENGINE RPM 
Engine RPM 
Hall Affect 
J1-24 ( - )
 
 
 
 
 
J1-25 ( + )
 
23 
O2 DUTY CYCLE 
Oxygen Sensor Measured Duty Cycle 
Derived 
n/a
‹
 40
Appendix B
H-100 Control Panel Technical Manual