H-100 DIGITAL OUTPUTS
 H-100 
GenLink
  Number 
Number  
Signal Description 
Connector Pin
 
Starter Relay (reserved) 
J1-23
 
Fuel Relay (reserved) 
J1-11
 
Fault Relay (reserved) 
J1-34
 
13.3L Gas Relay (reserved for ILC on 13.3L gas) 
J1-22
 5 
Auxiliary 
#1 
J2-23
 6 
Auxiliary 
#2 
J2-22
 7 
Auxiliary 
#3 
J2-33
 8 
Auxiliary 
#4 
J2-21
 
13.3L Ignition Module (reserved for ILC on 13.3L gas) 
J2-32
 
10 
n/a 
Overspeed Shutdown (reserved – no software control) 
J1-10
 
11 
28 
Throttle Driver PWM (reserved for H-100 governed generators) 
J1-33
 
12 
25 
PreHeat Relay – diesel only (reserved) 
J1-21
 
 
26 
Air/Fuel Ratio PWM – gas only (reserved) 
 
13 
31 
AVR Field Control (reserved) 
J2-20
 
14 
32 
AVR Field Control (reserved) 
J2-8
‹
H-100 DIGITAL INPUTS
 
Number 
Default Signal Name 
Signal Description 
Connector Pin
 
AUTO SWITCH 
Key Switch in AUTO 
J2-5
 
MANUAL SWITCH 
Key Switch in MANUAL 
J2-28
 
EMERGENCY STOP 
Emergency Stop Status 
J2-16
 
REMOTE START 
Remote Start 
J2-4
 
DI1/USR CFG 05 
DI-1, 
J2-27
 
 
BAT CHRGR FAIL 
Battery Charger Fail
 
DI2/USR CFG 06 
DI-2, 
J2-15
 
 
RUPTURED BASIN 
Ruptured Basin,
 
 
PROP GAS LEAK 
Propane Gas Leak,
 
 
DI2/FUEL PRESSURE 
Low Fuel Pressure
 
DI3/USR CFG 07 
DI-3, 
J2-3
 
 
DI3/LINE POWER 
Line Power
 
DI4/USR CFG 08 
DI-4, 
J2-26
 
 
DI4/GEN POWER 
Generator Power
 
MODEM DCD 
Modem DCD 
J1-14
 
 
USR CFG 09 
User confi gurable (reserved if Modem)
 
10 
MODEM ENABLED 
Modem Enable 
J1-26
 
11 
GEN OVERSPEED 
Generator Overspeed Detected 
Internal
‹
  
41
Appendix B
H-100 Control Panel Technical Manual