IMMEDIATE = Alarms/Warnings with this qualifica-
tion only become active immediately after the engine 
has started.
Sensor Failure Check
When this field is set, the input sensor is checked 
for short circuit or open circuit failure. Normally 
each of the inputs are conditioned externally to be 4-
20mA current loops. Any currents outside this range 
indicate a sensor failure. This will cause an alarm to 
occur. The alarm can be selected to shut down the 
engine if so desired via the next field. The alarm will 
be entered in the alarm log.
Shutdown on Sensor Failure
When this field is set, the engine will shut down if 
there is a sensor failure. If the field is unchecked, the 
failure will just cause an alarm message to appear 
and the audible alarm to sound. The alarm will be 
entered in the alarm log.
OTHER ANALOG OPTIONS
Event Log
When set, the channel measurement is compared to 
the setpoint with either the GT or LT options. Once 
the condition is met (eg measurement GT setpoint) 
the event is logged along with a date/time stamp into 
the volatile memory based event log. Six other param-
eters that can be chosen by the customer will also be 
logged. Volatile means that when power is removed 
from the unit, the memory will be lost.
Analog Outputs
There are no analog outputs available for customiza-
tion.
ANALOG SENSOR RATINGS
Typically the sensors used by the manufacturer have 
the following ratings:
  Temperature 
35 - 300 deg. F
  Pressure 
0 - 150 psi
‹
‹
OUTPUT FUNCTIONS
Output functions are flags that are set/reset by the 
internal program to indicate a certain status, for 
example “Engine Running”. The Measurement Engine 
allows these flags to be treated as “channels” that can 
be made into alarms/warnings, display messages, 
operate real outputs and also be fed as inputs to the 
ILC. For example, use the “Ready To Start” output 
function to operate a relay by mapping it to a physical 
output via GenLink, or you could feed it into the ILC 
to do combinatorial logic.
See TABLE OF OUTPUT FUNCTIONS in appendix 
B.
SPARE ANALOG CHANNELS
Depending upon the particular configuration of your 
product, the following input channels may be avail-
able for custom measurements:
‹
General Information
H-100 Control Panel Technical Manual
  Channel # 
Normal function
 4 
Coolant 
level
 5 
Fuel 
Level
 6 
Spare
 7 
Throttle 
position
 
Oxygen sensor 0-1Vdc
 
Battery charge current 0-5Vdc