Carrier GT-G 사용자 설명서

다운로드
페이지 56
Indoor & Outdoor Split 
Geothermal Comfort Systems
Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05
31
50YCS042 / 38WQS042 With GAH042 
Performance capacities shown in thousands of Btuh.
WPD
HEATING - EAT 70
°F
COOLING - EAT 80/67 
°F
EWT 
°F
GPM
PSI
FT
CFM
HC
KW
HE
LAT
COP
HWC
TC
SC
KW
HR
EER
HWC
5.2
2.0
4.7
1150
1400
Operation not recommended
20
9.0
4.9
11.2
1150
Operation not recommended
1400
10.5
6.2
14.3
1150
26.5
2.62
17.5
91.3
2.96
3.6
1400
27.2
2.60
18.4
88.0
3.07
3.1
5.2
2.0
4.6
1150
31.3
2.71
22.0
95.2
3.38
4.1
50.5
33.1
1.67
56.2
30.3
1.6
1400
31.3
2.65
22.3
90.7
3.46
3.5
52.4
36.4
1.73
58.3
30.3
1.3
30
9.0
4.7
10.9
1150
31.4
2.71
22.2
95.3
3.40
4.3
49.9
32.6
1.62
55.4
30.9
1.6
1400
31.9
2.67
22.8
91.1
3.51
3.6
52.5
36.6
1.68
58.2
31.3
1.4
10.5
6.0
13.9
1150
31.6
2.71
22.4
95.4
3.42
4.4
49.3
32.2
1.57
54.6
31.4
1.7
1400
32.5
2.68
23.3
91.5
3.55
3.8
52.6
36.9
1.63
58.2
32.4
1.5
5.2
1.9
4.5
1150
35.8
2.80
26.3
98.9
3.75
4.8
48.6
32.2
1.94
55.2
25.1
2.7
1400
35.9
2.73
26.6
93.7
3.85
4.2
50.4
35.4
2.01
57.2
25.1
2.5
40
9.0
4.6
10.6
1150
36.1
2.81
26.5
99.1
3.76
5.0
48.0
31.7
1.87
54.4
25.6
2.5
1400
36.9
2.77
27.4
94.4
3.90
4.3
50.5
35.6
1.94
57.1
26.0
2.4
10.5
5.8
13.5
1150
36.3
2.82
26.7
99.3
3.77
5.2
47.3
31.3
1.81
53.5
26.1
2.3
1400
37.8
2.80
28.3
95.0
3.96
4.5
50.5
35.9
1.88
57.0
26.9
2.3
5.2
1.9
4.3
1150
40.4
2.88
30.6
102.5
4.11
5.6
46.7
31.3
2.21
54.2
21.1
3.8
1400
40.4
2.82
30.8
96.7
4.21
4.8
48.4
34.3
2.29
56.2
21.1
3.6
50
9.0
4.4
10.2
1150
40.7
2.91
30.8
102.8
4.10
5.8
46.0
30.8
2.13
53.3
21.6
3.4
1400
41.8
2.87
32.0
97.7
4.27
5.0
48.4
34.6
2.21
56.0
21.9
3.4
10.5
5.6
13.0
1150
41.1
2.94
31.1
103.1
4.10
6.0
45.4
30.4
2.05
52.4
22.1
2.9
1400
43.2
2.92
33.2
98.6
4.34
5.2
48.5
34.9
2.13
55.8
22.8
3.1
5.2
1.8
4.2
1150
44.5
2.98
34.3
105.8
4.37
6.3
45.3
31.0
2.44
53.6
18.6
4.6
1400
45.0
2.90
35.1
99.7
4.55
5.5
46.9
33.3
2.52
55.5
18.6
4.6
60
9.0
4.3
9.9
1150
45.2
3.02
34.9
106.4
4.38
6.5
45.4
30.4
2.36
53.4
19.3
4.2
1400
46.4
2.94
36.3
100.7
4.61
5.7
47.0
33.7
2.42
55.2
19.4
4.2
10.5
5.5
12.6
1150
45.9
3.06
35.4
106.9
4.40
6.7
45.5
29.9
2.27
53.2
20.0
3.8
1400
47.8
2.99
37.6
101.6
4.68
5.9
47.0
34.1
2.31
54.9
20.3
3.9
5.2
1.8
4.0
1150
48.6
3.08
38.1
109.1
4.62
7.0
43.9
30.8
2.67
53.0
16.4
5.5
1400
49.5
2.98
39.4
102.8
4.87
6.2
45.5
32.3
2.75
54.8
16.5
5.5
70
9.0
4.1
9.6
1150
49.6
3.13
38.9
109.9
4.65
7.3
44.7
30.0
2.58
53.5
17.3
5.0
1400
50.9
3.02
40.6
103.7
4.94
6.4
45.5
32.7
2.63
54.4
17.3
5.1
10.5
5.3
12.2
1150
50.6
3.17
39.8
110.8
4.67
7.5
45.5
29.3
2.49
54.0
18.2
4.6
1400
52.3
3.07
41.9
104.6
5.00
6.6
45.5
33.2
2.50
54.0
18.2
4.8
5.2
1.7
3.9
1150
53.0
3.16
42.2
112.7
4.91
7.9
41.7
29.8
2.97
51.8
14.0
6.3
1400
54.1
3.06
43.6
105.8
5.17
6.7
43.2
31.2
3.06
53.6
14.1
6.4
80
9.0
4.0
9.3
1150
54.3
3.23
43.2
113.7
4.92
8.1
42.5
29.1
2.87
52.3
14.8
5.8
1400
55.7
3.13
45.1
106.9
5.22
7.0
43.2
31.7
2.92
53.2
14.8
6.0
10.5
5.1
11.8
1150
55.5
3.30
44.2
114.7
4.93
8.4
43.2
28.4
2.77
52.7
15.6
5.4
1400
57.4
3.19
46.5
108.0
5.27
7.3
43.2
32.2
2.78
52.7
15.6
5.6
5.2
1.6
3.8
1150
57.5
3.25
46.4
116.3
5.19
8.7
39.5
28.8
3.27
50.7
12.1
7.1
1400
58.6
3.15
47.9
108.8
5.46
7.3
40.9
30.2
3.37
52.4
12.1
7.4
90
9.0
3.9
8.9
1150
58.9
3.34
47.5
117.5
5.17
9.0
40.2
28.1
3.16
51.0
12.7
6.7
1400
60.5
3.23
49.5
110.0
5.49
7.7
40.9
30.7
3.21
51.9
12.7
6.9
10.5
4.9
11.4
1150
60.4
3.43
48.7
118.6
5.16
9.4
41.0
27.4
3.05
51.4
13.4
6.3
1400
62.5
3.31
51.2
111.3
5.53
8.0
40.9
31.1
3.06
51.4
13.4
6.4
5.2
1.6
3.6
1150
37.5
28.2
3.65
50.0
10.3
8.0
1400
38.9
29.6
3.76
51.7
10.3
8.3
100
9.0
3.7
8.6
1150
38.2
27.6
3.53
50.3
10.8
7.5
1400
38.9
30.0
3.59
51.1
10.8
7.8
10.5
4.7
11.0
1150
38.9
26.9
3.41
50.6
11.4
7.1
1400
Operation not recommended
38.9
30.5
3.42
50.6
11.4
7.2
5.2
1.5
3.5
1150
35.6
27.6
4.04
49.4
8.8
8.9
1400
36.8
29.0
4.16
51.0
8.8
9.2
110
9.0
3.6
8.3
1150
36.2
27.0
3.91
49.6
9.3
8.4
1400
36.8
29.4
3.97
50.4
9.3
8.6
10.5
4.6
10.5
1150
36.9
26.3
3.77
49.7
9.8
7.9
1400
36.9
29.9
3.78
49.8
9.8
8.1
Rev: 12/12/03 B
Interpolation is permissable, extrapolation is not.
All entering air conditions are 80
°F DB and 67°F WB in cooling and 70°F DB in heating.
All performance data is based upon the lower voltage of dual voltage rated units.
Operation below 40
°F EWT is based on 15% antifreeze solution.
See performance correction tables for operating conditions other than those listed above.
Table does not reflect fan or pump power ISO corrections.