Carrier GT-G 사용자 설명서

다운로드
페이지 56
Carrier
Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05
32
50YCS048 / 38WQS048 With GAH048 
Performance capacities shown in thousands of Btuh.
WPD
HEATING - EAT 70
°F
COOLING - EAT 80/67 
°F
EWT 
°F
GPM
PSI
FT
CFM
HC
KW
HE
LAT
COP
HWC
TC
SC
KW
HR
EER
HWC
6.0
2.6
5.9
1300
1600
Operation not recommended
20
9.0
4.9
11.2
1300
Operation not recommended
1600
12.0
7.6
17.6
1300
30.1
3.01
19.8
91.4
2.93
4.2
1600
31.4
2.95
21.3
88.2
3.12
3.6
6.0
2.5
5.8
1300
34.2
2.99
24.0
94.3
3.35
4.8
54.9
35.5
1.91
61.4
28.7
1.7
1600
36.7
2.98
26.5
91.2
3.61
4.0
56.7
38.9
2.00
63.5
28.3
1.4
30
9.0
4.7
10.9
1300
34.8
3.04
24.4
94.8
3.35
5.0
54.9
35.7
1.84
61.1
29.9
1.7
1600
36.8
3.01
26.5
91.3
3.58
4.2
56.5
38.7
1.93
63.1
29.4
1.5
12.0
7.4
17.1
1300
35.4
3.10
24.8
95.2
3.35
5.1
54.8
35.9
1.76
60.9
31.1
1.8
1600
36.9
3.04
26.5
91.4
3.56
4.4
56.4
38.5
1.85
62.7
30.5
1.6
6.0
2.4
5.6
1300
37.9
3.07
27.4
97.0
3.61
5.6
53.4
34.9
2.19
60.9
24.4
3.0
1600
40.7
3.07
30.2
93.6
3.89
4.8
55.1
38.2
2.30
63.0
24.0
2.8
40
9.0
4.6
10.6
1300
39.1
3.13
28.4
97.8
3.66
5.8
53.3
35.1
2.11
60.5
25.3
2.8
1600
41.3
3.09
30.7
93.9
3.92
5.0
54.9
38.0
2.21
62.4
24.9
2.6
12.0
7.2
16.6
1300
40.3
3.19
29.4
98.7
3.71
6.0
53.2
35.2
2.03
60.1
26.3
2.6
1600
41.9
3.11
31.3
94.2
3.95
5.2
54.7
37.8
2.12
61.9
25.8
2.5
6.0
2.3
5.4
1300
41.6
3.16
30.8
99.6
3.86
6.4
51.9
34.2
2.47
60.3
21.0
4.3
1600
44.7
3.15
33.9
95.9
4.15
5.6
53.6
37.5
2.59
62.4
20.7
4.1
50
9.0
4.4
10.2
1300
43.4
3.21
32.4
100.9
3.95
6.7
51.7
34.4
2.38
59.9
21.8
3.8
1600
45.8
3.16
35.0
96.5
4.24
5.8
53.3
37.3
2.49
61.8
21.4
3.8
12.0
7.0
16.1
1300
45.2
3.27
34.0
102.2
4.05
6.9
51.6
34.6
2.29
59.4
22.6
3.3
1600
46.8
3.17
36.0
97.1
4.33
6.0
53.0
37.1
2.40
61.2
22.1
3.5
6.0
2.3
5.2
1300
46.9
3.26
35.8
103.4
4.21
7.3
50.1
33.6
2.71
59.4
18.5
5.3
1600
48.7
3.24
37.6
98.2
4.40
6.3
52.7
37.2
2.83
62.4
18.6
5.2
60
9.0
4.3
9.9
1300
48.5
3.31
37.2
104.5
4.29
7.5
50.1
33.6
2.62
59.1
19.2
4.8
1600
50.3
3.25
39.2
99.1
4.53
6.6
52.4
37.0
2.73
61.7
19.2
4.8
12.0
6.7
15.6
1300
50.1
3.36
38.6
105.7
4.37
7.7
50.1
33.6
2.52
58.8
19.9
4.3
1600
52.0
3.27
40.8
100.1
4.66
6.8
52.0
36.9
2.62
60.9
19.8
4.5
6.0
2.2
5.1
1300
52.2
3.36
40.7
107.2
4.55
8.1
48.4
32.9
2.96
58.5
16.4
6.3
1600
52.6
3.32
41.3
100.5
4.64
7.1
51.9
36.9
3.07
62.4
16.9
6.3
70
9.0
4.1
9.6
1300
53.6
3.40
42.0
108.1
4.62
8.4
48.5
32.8
2.86
58.3
17.0
5.8
1600
54.9
3.35
43.5
101.8
4.81
7.3
51.4
36.8
2.96
61.5
17.4
5.9
12.0
6.5
15.1
1300
54.9
3.44
43.2
109.1
4.68
8.6
48.7
32.7
2.76
58.1
17.7
5.3
1600
57.1
3.37
45.6
103.0
4.97
7.6
50.9
36.6
2.85
60.6
17.9
5.5
6.0
2.1
4.9
1300
56.1
3.45
44.3
110.0
4.77
9.0
46.6
32.1
3.26
57.7
14.3
7.2
1600
56.6
3.41
45.0
102.8
4.87
7.8
50.0
36.0
3.39
61.5
14.7
7.4
80
9.0
4.0
9.3
1300
57.2
3.48
45.4
110.8
4.82
9.4
46.7
32.0
3.15
57.5
14.8
6.7
1600
58.6
3.43
47.0
103.9
5.01
8.1
49.5
35.8
3.26
60.6
15.2
6.9
12.0
6.3
14.6
1300
58.4
3.52
46.4
111.6
4.86
9.7
46.9
31.9
3.04
57.2
15.4
6.3
1600
60.7
3.44
48.9
105.1
5.16
8.4
49.0
35.7
3.14
59.7
15.6
6.4
6.0
2.0
4.7
1300
60.1
3.53
48.0
112.8
4.98
10.0
44.8
31.3
3.57
57.0
12.6
8.2
1600
60.6
3.49
48.7
105.1
5.08
8.4
48.0
35.0
3.71
60.7
13.0
8.5
90
9.0
3.9
8.9
1300
60.9
3.56
48.8
113.4
5.01
10.4
44.9
31.2
3.45
56.7
13.0
7.7
1600
62.4
3.51
50.4
106.1
5.21
8.8
47.6
34.9
3.57
59.7
13.3
8.0
12.0
6.1
14.0
1300
61.8
3.60
49.5
114.0
5.04
10.8
45.1
31.1
3.33
56.4
13.6
7.2
1600
64.2
3.52
52.2
107.2
5.35
9.2
47.1
34.8
3.43
58.8
13.7
7.4
6.0
2.0
4.5
1300
43.1
30.9
3.99
56.7
10.8
9.3
1600
46.3
34.6
4.14
60.4
11.2
9.6
100
9.0
3.7
8.6
1300
43.3
30.8
3.85
56.4
11.2
8.7
1600
45.8
34.5
3.99
59.4
11.5
9.0
12.0
5.9
13.5
1300
43.4
30.7
3.72
56.1
11.7
8.2
1600
Operation not recommended
45.4
34.4
3.84
58.4
11.8
8.4
6.0
1.9
4.4
1300
41.5
30.6
4.41
56.5
9.4
10.3
1600
44.5
34.2
4.58
60.1
9.7
10.7
110
9.0
3.6
8.3
1300
41.6
30.5
4.26
56.1
9.8
9.7
1600
44.1
34.1
4.41
59.1
10.0
10.0
12.0
5.6
13.0
1300
41.7
30.4
4.11
55.8
10.2
9.2
1600
43.6
34.0
4.24
58.1
10.3
9.4
Rev: 12/12/03 B
Interpolation is permissable, extrapolation is not.
All entering air conditions are 80
°F DB and 67°F WB in cooling and 70°F DB in heating.
All performance data is based upon the lower voltage of dual voltage rated units.
Operation below 40
°F EWT is based on 15% antifreeze solution.
See performance correction tables for operating conditions other than those listed above.
Table does not reflect fan or pump power ISO corrections.