33
50YCS060 / 38WQS060 With GAH060
Performance capacities shown in thousands of Btuh.
WPD
HEATING - EAT 70
°F
COOLING - EAT 80/67 
°F
EWT 
°F
GPM
PSI
FT
CFM
HC
KW
HE
LAT
COP
HWC
TC
SC
KW
HR
EER
HWC
7.5
1.6
3.7
1650
2000
Operation not recommended
20
11.3
3.2
7.4
1650
Operation not recommended
2000
15.0
5.1
11.8
1650
41.1
4.04
27.3
93.0
2.98
5.3
2000
41.5
3.99
27.9
89.2
3.05
4.5
7.5
1.6
3.6
1650
43.1
4.09
29.2
94.2
3.09
6.0
67.5
44.2
2.64
76.5
25.5
2.2
2000
43.8
4.05
30.0
90.3
3.17
5.0
69.1
47.2
2.73
78.5
25.3
1.8
30
11.3
3.1
7.1
1650
45.5
4.13
31.4
95.5
3.23
6.2
67.6
43.9
2.58
76.4
26.2
2.3
2000
46.1
4.09
32.2
91.4
3.30
5.3
68.8
46.7
2.68
77.9
25.7
1.9
15.0
4.9
11.4
1650
47.9
4.18
33.6
96.9
3.36
6.4
67.6
43.6
2.52
76.2
26.9
2.3
2000
48.5
4.13
34.4
92.4
3.44
5.5
68.4
46.1
2.63
77.4
26.0
2.0
7.5
1.5
3.5
1650
50.4
4.29
35.8
98.3
3.45
7.0
65.3
43.5
3.05
75.7
21.4
3.8
2000
51.3
4.25
36.8
93.7
3.54
6.0
66.8
46.5
3.15
77.6
21.2
3.5
40
11.3
3.0
6.9
1650
53.0
4.35
38.2
99.8
3.57
7.3
65.4
43.3
2.96
75.5
22.1
3.5
2000
53.3
4.28
38.7
94.7
3.65
6.2
66.5
46.0
3.07
77.0
21.7
3.4
15.0
4.8
11.1
1650
55.7
4.42
40.6
101.3
3.69
7.5
65.5
43.0
2.86
75.2
22.9
3.2
2000
55.3
4.32
40.6
95.6
3.75
6.5
66.3
45.5
2.99
76.5
22.1
3.2
7.5
1.5
3.4
1650
57.7
4.48
42.4
102.4
3.77
8.0
63.1
42.9
3.46
74.9
18.2
5.4
2000
58.7
4.44
43.5
97.2
3.87
7.0
64.6
45.8
3.58
76.8
18.1
5.2
50
11.3
2.9
6.7
1650
60.6
4.57
45.0
104.0
3.88
8.3
63.2
42.6
3.34
74.6
18.9
4.8
2000
60.4
4.48
45.2
98.0
3.96
7.2
64.3
45.3
3.47
76.1
18.6
4.8
15.0
4.6
10.7
1650
63.5
4.66
47.6
105.6
3.99
8.6
63.3
42.4
3.21
74.2
19.7
4.1
2000
62.2
4.51
46.8
98.8
4.04
7.5
64.1
44.8
3.36
75.5
19.1
4.4
7.5
1.4
3.3
1650
64.9
4.68
48.9
106.4
4.06
9.1
61.6
41.9
3.78
74.6
16.3
6.6
2000
66.1
4.64
50.3
100.6
4.17
7.9
63.1
45.4
3.90
76.4
16.2
6.5
60
11.3
2.8
6.5
1650
68.1
4.79
51.7
108.2
4.16
9.4
61.9
41.7
3.61
74.2
17.1
6.0
2000
68.5
4.67
52.6
101.7
4.30
8.2
63.2
45.0
3.74
75.9
16.9
6.1
15.0
4.5
10.4
1650
71.3
4.90
54.5
110.0
4.26
9.7
62.1
41.4
3.45
73.9
18.0
5.4
2000
71.0
4.71
54.9
102.9
4.42
8.5
63.2
44.6
3.58
75.4
17.7
5.6
7.5
1.4
3.2
1650
72.2
4.88
55.5
110.5
4.33
10.1
60.2
41.0
4.11
74.2
14.7
7.8
2000
73.5
4.83
57.0
104.0
4.45
8.9
61.7
45.0
4.23
76.1
14.6
7.9
70
11.3
2.7
6.3
1650
75.6
5.01
58.5
112.4
4.42
10.4
60.6
40.7
3.89
73.9
15.6
7.2
2000
76.6
4.87
60.0
105.5
4.61
9.2
62.0
44.7
4.02
75.7
15.4
7.3
15.0
4.3
10.0
1650
79.0
5.15
61.5
114.4
4.50
10.8
61.0
40.4
3.68
73.5
16.6
6.6
2000
79.7
4.90
63.0
106.9
4.77
9.5
62.4
44.3
3.80
75.4
16.4
6.8
7.5
1.3
3.1
1650
79.4
5.08
62.1
114.6
4.58
11.3
57.6
40.2
4.56
73.2
12.6
9.0
2000
80.9
5.03
63.7
107.5
4.71
9.7
59.0
44.2
4.70
75.0
12.5
9.2
80
11.3
2.6
6.1
1650
82.7
5.20
64.9
116.4
4.66
11.7
58.0
40.0
4.32
72.7
13.4
8.4
2000
83.8
5.05
66.6
108.8
4.86
10.1
59.3
43.8
4.46
74.5
13.3
8.6
15.0
4.2
9.7
1650
86.0
5.33
67.8
118.2
4.73
12.1
58.3
39.7
4.09
72.3
14.3
7.8
2000
86.7
5.07
69.4
110.1
5.01
10.5
59.7
43.5
4.22
74.1
14.1
8.0
7.5
1.3
3.0
1650
86.7
5.28
68.7
118.7
4.81
12.5
55.0
39.5
5.02
72.1
11.0
10.2
2000
88.3
5.23
70.5
110.9
4.95
10.5
56.3
43.4
5.17
73.9
10.9
10.6
90
11.3
2.5
5.9
1650
89.8
5.39
71.4
120.4
4.88
13.0
55.3
39.2
4.76
71.5
11.6
9.6
2000
91.0
5.24
73.1
112.1
5.09
11.0
56.6
43.0
4.90
73.3
11.5
9.9
15.0
4.1
9.4
1650
92.9
5.51
74.1
122.1
4.94
13.5
55.6
39.0
4.49
71.0
12.4
9.0
2000
93.7
5.25
75.8
113.4
5.23
11.5
56.9
42.7
4.64
72.8
12.3
9.2
7.5
1.2
2.9
1650
53.3
39.1
5.56
72.3
9.6
11.5
2000
54.6
42.9
5.72
74.1
9.5
11.9
100
11.3
2.4
5.6
1650
53.7
38.8
5.27
71.6
10.2
10.8
2000
54.9
42.6
5.43
73.5
10.1
11.2
15.0
3.9
9.0
1650
54.0
38.5
4.98
71.0
10.8
10.2
2000
Operation not recommended
55.3
42.2
5.14
72.8
10.7
10.4
7.5
1.2
2.8
1650
51.7
38.6
6.10
72.5
8.5
12.8
2000
52.9
42.5
6.28
74.4
8.4
13.3
110
11.3
2.4
5.4
1650
52.0
38.4
5.78
71.8
9.0
12.1
2000
53.3
42.1
5.96
73.6
8.9
12.5
15.0
3.8
8.7
1650
52.4
38.1
5.46
71.0
9.6
11.4
2000
53.6
41.8
5.64
72.8
9.5
11.6
Rev: 12/12/03 B
Interpolation is permissable, extrapolation is not.
All entering air conditions are 80
°F DB and 67°F WB in cooling and 70°F DB in heating.
All performance data is based upon the lower voltage of dual voltage rated units.
Operation below 40
°F EWT is based on 15% antifreeze solution.
See performance correction tables for operating conditions other than those listed above.
Table does not reflect fan or pump power ISO corrections.