LOG AND EMBER INSTALLATION
WARNING:  Dangerous operating conditions may occur if these 
logs are not positioned in their approved locations.  Read the 
instructions below carefully and refer to the diagrams. If logs are 
broken do not use the unit until they are replaced. Broken logs 
can interfere with the pilot and burner operation.
The gas log kit contains the following:
 a) 
Front 
Log
 b) 
Rear 
Log 
 
c)  Small Cross Logs (2)
 
d)  Bag of embers
 
e)  Bag of rock wool
 
1)  Remove the logs from the box and carefully unwrap them.  The logs 
are fragile, handle with care.  Do not force into position.  
2)  Place the rear defl ector on the rear log support pins in the back of 
the unit.
3)  Place the rear log into the rear of the fi rebox, aligning the holes on 
the underside of the log with the rear log support pins and carefully 
push the log down onto the pins. See diagrams 1 and 2.
4)  Ensure the front defl ector is over front log pins.  See diagram 1.
5)  Place the front log in the front of the unit, aligning the holes on the 
underside of the log with the log support pins in the front of the 
unit.  Carefully push the log down onto the pins. See diagram 1.
6)  Place the cross logs on top of the larger logs aligning the holes on 
the underside of the cross log with the log pins in the larger logs.  
See diagrams 1 & 2. Carefully push the cross logs onto the pins.
Diagram 1
TEST FOR FLUE SPILLAGE
This heater must be properly connected to a fl ue system.
WARNING: Operation of this heater when not connected to a 
properly installed and maintained fl ue system or tampering with 
the fl ue safety shutoff system can result in carbon monoxide (CO) 
poisoning and possible death.
A “spillage” test must be made before the installed unit is left with the 
customer.  Follow the procedure below:
1)  Start all exhaust fans in the home and then close all doors and 
windows in the room.
2)  Light the unit and set controls to maximum.
3)  After fi ve minutes, test that there is a “pull” on the fl ue by placing 
a smoke match, cigarette or similar device which gives off smoke, 
on the edge of the draft hood. See Diagram below.
The smoke should be drawn into the draft hood. If the smoke is still 
not drawn into the draft hood, turn the unit off and check for the cause 
of the lack of draft and rectify before proceeding.
Note: If the fl ue is blocked or has a strong reverse fl ow, the thermally 
actuated safety switch mounted in the draft hood will automatically 
shut off the gas supply in less than 10 minutes. If the heater turns 
off because of this during the spillage test, check for the cause 
of the lack of draft and rectify before proceeding.
To reset the thermally actuated safety switch, let the unit cool for 
10 minutes, then press the red reset button on the back of the 
switch. See Diagram.
INSTALLATION