 F33-3 Freestanding Gas Stove
9
                                                                                       
INSTALLATION
SYSTEM DATA
                                       NG
      
           LPG
Injector size 
# 36 
# 52
Input Rating 
33 mj  
33 mj
Manifold Pressure 
0.8 kPa 
2.38 kPa
GAS PIPE PRESSURE TESTING
The appliance must be isolated from the gas supply piping system 
by closing its individual manual shut-off valve during any pressure 
testing of the gas supply piping system at test pressures equal to or 
less than 3.45 kPa.  Disconnect piping from valve at pressures over  
3.45 kPa.
The manifold pressure is controlled by a regulator built into the gas 
control, and should be checked at the pressure test point.
Note: 
To properly check gas pressure, both inlet and manifold 
pressures should be checked using the valve pressure 
ports on the valve.
1)  Make sure the valve is in the "OFF" position.
2)  Loosen the "IN" and/or "OUT" pressure tap(s), turning counter-
clockwise with a 1/8" wide fl at screwdriver.
3)  Attach manometer to "IN" and/or "OUT" pressure tap(s) using a 
5/16" ID hose.
GAS CONNECTION
The gas connection is a 1/2 inch BSP Male thread. The gas line can 
be rigid copper pipe. Pipe size to ensure correct operating pressure.  
For minimum and maximum supply pressure see the System Data 
table below.
Note: 
During any pressure testing of the gas supply piping 
system that exceeds test pressures of 3.45 kPa, this ap-
pliance and its individual shut-off valve must be discon-
nected from the piping system.  If test pressures equal to 
or less than 3.45 kPa are used then this appliance can be 
isolated from the piping system by closing its individual 
manual shut-off valve, if fi tted, during the testing.
INSTALLATION IS TO BE CARRIED OUT 
ONLY BY AN AUTHORISED PERSON
4)  Light the pilot and turn the valve to "ON" position.
5)  The pressure check should be carried out with the unit burning 
and the setting should be within the limits specifi ed on the safety 
label.
6)  When fi nished reading manometer, turn off the gas valve, discon-
nect the hose and tighten the screw (clockwise) with a 1/8" fl at 
screwdriver. Screw should be snug, but do not over tighten.
1) Gas 
on/off 
knob
2)  Manual high/low adjustment
3) Pilot 
Adjustment
4) Thermocouple 
Connection
5) Main 
Operator
6)  Outlet Pressure Tap
7) Inlet 
Pressure 
Tap
8) Pilot 
Outlet
9)  Main Gas Outlet
VALVE DESCRIPTION
10) Flange Securing Screw Holes
11) Alternative TC Connection Point
12) Thermoelectric Unit
13) Additional Valve Mounting Hole