REDUCED CLEARANCES 
You  may  decrease the clearances by installing heat radiation shields between the walls or 
the ceiling and the stove.  These heat radiation shields must be installed permanently, and 
can include sheet metal, a rigid non-combustible sheet or a masonry wall. 
 
Clearances of not less than 1" (25 mm) and not more than 3" (76 mm) between the bottom 
of the shield and the floor and not less than 3" (76 mm) between the top of the shield and 
the ceiling must be respected to allow vertical air circulation behind the shield. 
 
The shield must extend 20" (500 mm) above the stove top and 18" (450mm) to each side of 
the stove. 
 
Following  the  installation  of  such  a  heat  radiation  shield,  the  clearances  mentioned  on  the 
stove certification plate may be reduced as stated in the following table. 
 
 
Reducing Clearances With 
Shielding 
TYPE OF PROTECTION 
Sides and 
Rear/Back 
Top 
Sheet  metal, a minimum of 0,013" (0,33 mm) spaced 
out at least 7/8" (21 mm) by non-combustible spacers. 
67% 
50% 
Ceramic  tiles,  or  an  equivalent  non-combustible 
material on fire-proof supports spaced out at least 7/8" 
(21 mm) by non-combustible spacers. 
50% 
33% 
Ceramic  tiles,  or  an  equivalent  non-combustible 
material  on  fire-proof  supports  with  a  minimum  of 
0,013"  (0,33  mm)  sheet  metal  backing  spaced  out  at 
least 7/8" (21 mm) by non-combustible spacers. 
67% 
50% 
Brick  spaced  out  at  least  7/8"  (21  mm)  by  non-
combustible spacers. 
50% 
N/A 
Brick with a minimum of 0,013" (0,33 mm) sheet metal 
backing spaced out at least 7/8" (21 mm) by non-
combustible spacers. 
 
67% 
N/A 
Source: CSA Standard B365-1991, Table 4, Page 27