Change during operation: N = impossible, Y* = possible (enabled by using             ), Y= possible (enabled by using 
 
 ) 
 
 
-55- 
FUNC 
DATA
 
 
               Operation time
 
 
This function displays the integration time of power supply applied to the drive. 
0 to 655 are displayed to indicate 0 to 65500 hours. 
If the integration time exceeds 65500 hours, 65500 is displayed continuously.  While the total of power 
supply times is less than one hour, the times are not integrated.
 
 
               Trip history
 
 
 
This function memorizes the history of the last four protection operations. 
Each data item can be called using the 
 key.
 
The calling procedure is shown below:
 
No. 
Procedure 
Display ex-
ample 
Remarks 
           Call   H 0
2  
H 0
2  
 
O U 2  
The contents (history) of the latest 
alarm are displayed. 
O H 2  
The contents of the second latest alarm 
are displayed. 
O C
1  
The contents of the third latest alarm 
are displayed. 
Press the         
  
FUNC
DATA
 key  
 
Press the 
    
 key  
  
Press the 
    
 key      
  
Press the 
    
 key 
Press the 
      
 key  
       
Press the 
      
 key 
       
Press the 
      
 key 
       
Press the 
      
 key  
 
-
-
-  
The contents of the fourth latest alarm 
are displayed. (This example is for no 
history.) 
Press the 
    
 key 
 
E n
d  
 
 
The contents of a new alarm is stored in the data area for the history of the latest alarm.  At this time, the 
history of the latest alarm is stored in the data area for the second latest alarm. The histories of the second 
and third latest alarms are moved in this way and the history of the fourth latest alarm is deleted. 
Stored trip histories are not deleted although data initialization is executed with H03.
 
H02 
Factory  
setting
 
--- 
Change during 
operation 
Monitoring only.
 
 
Factory  
setting
 
Change during  
operation 
Monitoring only.
 
 
H01