Change during operation: N = impossible, Y* = possible (enabled by using             ), Y= possible (enabled by using 
 
 ) 
 
 
-56- 
FUNC 
DATA
 
 
 
                Data initialization 
 
This function initializes data items set with all functions to values set in the factory.
 
    0
 
Manually set value
 
    1
 
Initialized (factory set value )
 
 
The display is changed from 
    0  
to 
    1
 when the 
STOP  
and 
 keys are pressed simultane-
ously. 
When the 
FUNC
DATA
 key is pressed under this condition, initial data is written and a frequency set by the 
built-in POT (VR) is displayed automatically.
 
 
 
               Auto Reset 
 
  This function selects a retry operation if the drive is tripped. 
 
    0
 : 
Inactive
 
  to
 
    1
 : 
The auto reset count is fixed to 5 and auto reset starts when 0.5s elapses after tripping . 
Auto reset is attempted only for an overcurrent/overvoltage trip that occurs during operation.
 
 
 
 
 
               Fan stop operation 
 
    0  : 
ON-OFF No control (always on) 
    1
 : 
ON-OFF Control
 
(The fan is turned off when the drive temperature becomes low after operation is 
stopped.)
 
 
 
               PID control (Mode select) 
 
    0
 : 
Inactive
          
    1
 : 
Active (Normal)
 
                    
    2
 : 
Active (Inverse)
    
The feedback signal value (%) is displayed by assuming the full scale to be 100% when a PID control 
operation is selected.
Factory 
setting 
Change during 
operation 
N
 
H20 
Factory 
setting 
Change during 
operation 
N
 
H03 
Factory 
setting 
Change during 
operation 
Y* 
H04 
H06 
Factory 
setting 
Change during 
operation 
Y* 
Select a PID control operation.