Change during operation: N = impossible, Y* = possible (enabled by using             ), Y= possible (enabled by using 
 
 ) 
 
 
-57- 
FUNC 
DATA
 
 
  PID control  
             (Feedback signal)
 
This function selects a PID control feedback signal.
 
    0   Terminal 12
(0 to +10Vdc)
 
    1  
 
Terminal C1
(4 to 20mAdc)
 
    2  
 
Terminal 12
(+1 to +5Vdc) 
 
 
  PID control (P-gain)
 
 
 This function sets a P-gain. 
  0. 0 1  to  1 0. 0   P-gain from 0.01 to 10.0 times (1 to 1000%) (in increment of 0.01 step)
 
 
 
 
 
 PID control (I-gain)
 
 
This function sets an integral time. 
  0. 0           :  No integration 
  0. 1  to  9 9 9   :  Integral time 0.1 to 999s  
(in 0.1s step for 99.9s or less, 1s step for 100s or more) 
 
 
  
PID control (D-gain)
 
 
This function sets a derivative time. 
0. 0 0           : No derivative 
0. 0 1  to  1 0. 0   : Derivative time 0.01 to 10.0s (in 0.01s step) 
 
 
  PID control  
   (Feedback filter) 
 
This function sets a filter time constant of PID feedback. 
  0. 0  to  6 0. 0  : Time constants 0.0 to 60.0s (in 0.1s step)
 
 
Factory 
setting 
Change during 
operation 
N
 
H21 
H24 
H25 
H22 
H23 
Factory 
setting 
Change during 
operation 
0.01 
Factory 
setting 
Change during 
operation 
0.0s 
Factory 
setting 
Change during 
operation 
0.00s 
Factory 
setting 
Change during 
operation 
0.5s