“B” Group: Fine-Tuning Functions
Configur
ing Dr
iv
P
a
ra
meters
3–46
External Brake 
Control
The brake control function in the inverter controls external braking used in systems such as 
elevators. The purpose of this function is to ensure the inverter is powering the motor before 
releasing external brakes that would permit the load to move or coast. This function requires the 
configuration and wiring of intelligent input and output terminals. See 
 for more information.
“B” Function
Run 
Mode
Edit
Lo Hi
Defaults
Units
SRW Display
Func.
Code
Name
Description
–FE
(CE)
–FU
(UL)
–FR
(Jpn)
B120
Brake Control Enable
Two option codes:
00 Disable
01 Enable
✘ ✔
00
00
00
>b120 BRAKE
Mode         OFF
B121
Brake Wait Time for 
Release
Sets time delay between 
arrival at release frequency 
and the brake release signal.
Range is 0.00 to 5.00 sec.
✘ ✔ 0.00 0.00 0.00
sec.
>b121 BRAKE
STA-WAIT   0.00s
B122
Brake Wait Time for 
Acceleration
Sets time delay after brake 
confirmation signal is 
received until the inverter 
begins acceleration
Range is 0.00 to 5.00 sec.
✘ ✔ 0.00 0.00 0.00
sec.
>b122 BRAKE
ACC-WAIT   0.00s
B123
Brake Wait Time for 
Stopping
Sets time delay after brake 
confirmation signal turns 
OFF until decelerating the 
inverter to 0 Hz.
Range is 0.00 to 5.00 sec.
✘ ✔ 0.00 0.00 0.00
sec.
>b123 BRAKE
STP-WAIT   0.00s
B124
Brake Wait Time for 
Confirmation
Sets the wait time for confir-
mation after turn ON/OFF of 
brake release. If confirma-
tion is not received during 
the specified wait time, the 
inverter will trip with an 
external brake error.
Range is 0.00 to 5.00 sec.
✘ ✔ 0.00 0.00 0.00
sec.
>b124 BRAKE
BRK-WAIT   0.00s
B125
Brake Release 
Frequency Setting
Sets the frequency at which 
the inverter will output the 
brake release signal after 
delay set by B121.
Range is 0.00 to 99.99 /
100.0 to 400.0Hz
✘ ✔ 0.00 0.00 0.00
Hz
>b125 BRAKE
OPEN-F  000.00Hz
B126
Brake Release Current 
Setting
Sets the minimum inverter 
current level above which 
the brake release signal will 
be permitted.
Range is 0% to 200% of 
rated current
✘ ✔
Rated current for 
each inverter model
A
>b126 BRAKE
OPEN-A   00.16.5A
[BRK] Brake release
[BOK] Brake confirmation
Inverter
External Brake 
System
Emergency Brake
(or alarm, etc.)
[BER] Brake error