SJ300 Inverter
Configur
ing Dr
iv
P
a
ra
met
e
rs
3–49
Intelligent Input 
Terminal 
Overview
Each of the eight intelligent terminals may be assigned any of the options in the following 
table. When you program one of the option codes for terminal assignments C001 to C008, the 
respective terminal assumes the function role of that option code. The terminal functions have a 
symbol or abbreviation, which we use to label a terminal using that function. For example the 
“Reverse Run” command is [RV]. The physical label on the terminal block connector is simply 
123456, 7, or 8. However, schematic examples in this manual also use the terminal 
function symbol (such as [RV]) to show the assigned option. The option codes for C011 to 
C019 determine the active state of the logical input (active high or active low).
Summary Table - This table shows all forty-four intelligent input functions at a glance. 
Detailed descriptions of these functions, related parameters and settings, and example wiring 
diagrams are in 
.
Input Function Summary Table
Option
Code
Terminal 
Symbol
Function Name
Description
01
RV
Reverse Run/Stop
ON
Inverter is in Run Mode, motor runs reverse
OFF
Inverter is in Stop Mode, motor stops
02
CF1
Multi-speed select,
Bit 0 (LSB)
ON
Binary encoded speed select, Bit 0, logical 1
OFF
Binary encoded speed select, Bit 0, logical 0
03
CF2
Multi-speed select,
Bit 1
ON
Binary encoded speed select, Bit 1, logical 1
OFF
Binary encoded speed select, Bit 1, logical 0
04
CF3
Multi-speed select,
Bit 2
ON
Binary encoded speed select, Bit 2, logical 1
OFF
Binary encoded speed select, Bit 2, logical 0
05
CF4
Multi-speed select,
Bit 3 (MSB)
ON
Binary encoded speed select, Bit 3, logical 1
OFF
Binary encoded speed select, Bit 3, logical 0
06
JG
Jogging
ON
Inverter is in Run Mode, output to motor runs at jog 
parameter frequency A038
OFF
Inverter is in Stop Mode
07
DB
External Signal for DC 
Injection Braking
ON
DC braking will be applied during deceleration
OFF
DC braking will not be applied
08
SET
Set (select) 2nd Motor 
Data
ON
The inverter uses 2nd motor parameters for generat-
ing frequency output to motor
OFF
The inverter uses 1st (main) motor parameters for 
generating frequency output to motor
09
2CH
2-stage Acceleration 
and Deceleration
ON
Frequency output uses 2nd-stage acceleration and 
deceleration values
OFF
Frequency output uses standard acceleration and 
deceleration values
11
FRS
Free-run Stop
ON
Causes output to turn OFF, allowing motor to free run 
(coast) to stop
OFF
Output operates normally, so controlled deceleration 
stops motor
12
EXT
External Trip
ON
When assigned input transitions OFF to ON, inverter 
latches trip event and displays E12
OFF
No trip event for ON to OFF transition; any recorded 
trip events remain in history until Reset