“C” Group: Intelligent Terminal Functions
Configur
ing Dr
iv
P
a
ra
meters
3–50
13
USP
Unattended Start 
Protection
ON
On powerup, the inverter will not resume a Run 
command (mostly used in the US)
OFF
On powerup, the inverter will resume a RUN 
command that was active before power loss
14
CS
Commercial Power 
Source
ON
OFF-to-ON transition signals the inverter that the 
motor is already running at powerup (via bypass), 
thus suppressing the inverter’s motor output in Run 
Mode
OFF
ON-to-OFF transition signals the inverter to apply a 
time delay (B003), frequency match its output to 
existing motor speed, and resume normal Run Mode 
operation
15
SFT
Software Lock
ON
The keypad and remote programming devices are 
prevented from changing parameters
OFF
The parameters may be edited and stored
16
AT
Analog Input Voltage/
current Select
ON
If A005=00, terminal [OI] is enabled for  input.
If A005=01, terminal [O2] is enabled for input.
(Use terminal [L] for signal return.)
OFF
Terminal [O] is enabled for voltage input
(Use terminal [L] for signal return)
17
SET3
Set (select) 3rd motor 
data
ON
The inverter uses 3rd motor parameters for generating 
frequency output to motor
OFF
The inverter uses 1st (main) motor parameters for 
generating frequency output to motor
18
RS
Reset Inverter
ON
The trip condition is reset, the motor output is turned 
OFF, and powerup reset is asserted
OFF
Normal power-on operation
20
STA
START
(3-wire interface)
ON
Starts the motor rotation
OFF
No change to present motor status
21
STP
STOP
(3-wire interface)
ON
Stops the motor rotation
OFF
No change to present motor status
22
F/R
FWD, REV
(3-wire interface)
ON
Selects the direction of motor rotation: ON = FWD.
While the motor is rotating, a change of F/R will start 
a deceleration, followed by a change in direction.
OFF
Selects the direction of motor rotation: OFF =REV.
While the motor is rotating, a change of F/R will start 
a deceleration, followed by a change in direction.
23
PID
PID Disable
ON
Temporarily disables PID loop control. Inverter 
output turns OFF as long as PID Enable is active 
(A071=1).
OFF
Has no effect on PID loop operation, which operates 
normally if PID Enable is active (A071 = 1).
Input Function Summary Table
Option
Code
Terminal 
Symbol
Function Name
Description