Hitachi SJ300-037HFE 사용자 설명서

다운로드
페이지 289
“C” Group: Intelligent Terminal Functions
Configur
ing Dr
iv
P
a
ra
meters
3–52
39
OLR
Overload restriction
ON
Selects current overload parameter set 2
(B024, B025, B026)
OFF
Selects current overload parameter set 1
(B021, B022, B023)
40
TL
Torque limit enable
ON
Enables torque limit feature
OFF
Disables all torque limit sources. Defaults to 200% of 
inverter rated torque output.
41
TRQ1
Torque limit selection, 
bit 1 (LSB)
ON
Logical 1
OFF
Logical 0
42
TRQ2
Torque limit selection, 
bit 2 (MSB)
ON
Logical 1
OFF
Logical 0
43
PPI
Proportional / 
Proportional/Integral 
mode selection
ON
Selects Proportional-only control
OFF
Selects Proportional-Integral control
44
BOK
Brake confirmation 
signal
ON
Indicates external brake has released (used only for 
external brake control function)
OFF
Indicates the external brake has not yet released
45
ORT Orientation 
(home 
search)
ON
The encoder is in the home (oriented) position
OFF
The encoder position is not in the home position
46
LAC
LAC: LAD cancel
ON
Disables the Linear Accel / Decel (LAD) mode
OFF
Normal Linear Accel / Decel mode
47
PCLR
Position deviation reset
ON
Clears the position deviation by setting the actual 
position equal to the desired position
OFF
Position count operates normally
48
STAT
Pulse train position 
command input enable
ON
Enables the pulse train control of motor
OFF
Disables pulse train control of motor
no
Not selected
ON
(input ignored)
OFF
(input ignored)
Input Function Summary Table
Option
Code
Terminal 
Symbol
Function Name
Description