Hitachi SJ300-037HFE 사용자 설명서

다운로드
페이지 289
SJ300 Inverter
Configur
ing Dr
iv
P
a
ra
met
e
rs
3–59
Serial
Communications
The following table configures the communications port of the SJ300 inverter. You can have up 
to thirty-two devices on the serial communications network. The inverters are slaves and the 
computer or digital operator is the master. Thus, all inverters on the serial connection must use 
the same baud rate, data length, parity, and stop bits. However, each device on the serial 
network must have a unique node address. See 
 for more 
information.
“C” Function
Run 
Mode
Edit
Lo Hi
Defaults
Units
SRW Display
Func.
Code
Name
Description
–FE
(CE)
–FU
(UL)
–FR
(Jpn)
C070
Data command method
Four option codes:
02 Digital operator
03 RS485
04 Expansion card #1
05 Expansion card #2
✘ ✘
02
02
02
>C070 PARAM
SELECT      REM
C071
Communication speed 
selection
Five option codes:
02 (Test)
03 2400bps
04 4800bps
05 9600bps
06 19200bps
✘ ✔
04
04
04
bps
>C071 RS485
BAU     4800bps
C072
Node allocation
Set the address of the 
inverter on the network. 
Range is 1 to 32.
✘ ✔
1.
1.
1.
>C072 RS485
ADDRESS       01
C073
Communication data 
length selection
Two option codes:
07 7-bit data
08 8-bit data
✘ ✔
7
7
7
>C073 RS485
BIT         7BIT
C074
Communication parity 
selection
Three option codes:
00 No parity
01 Even parity
02 Odd parity
✘ ✔
00
00
00
>C074 RS485
PARITY        NO
C075
Communication stop bit 
selection
Two option codes:
01 1 stop bit
02 2 stop bits
✘ ✔
1
1
1
>C075 RS485
STOPBIT     1BIT
C078
Communication wait 
time
Time the inverter waits after 
receiving a message before it 
transmits. Range is 0.0 to 
1000 ms
✘ ✔
0.
0.
0.
>C078 RS485
WAIT      0000ms