“C” Group: Intelligent Terminal Functions
Configur
ing Dr
iv
P
a
ra
meters
3–60
Analog Signal 
Calibration 
Settings
The functions in the following table configure the signals for the analog output terminals. Note 
that these settings do not change the current/voltage or sink/source characteristics – only the 
zero and span (scaling) of the signals.
NOTE: Settings C081, C082, C083, C121, C122, C123 are factory-calibrated for each inverter. 
Do not change these settings unless absolutely necessary. Note that if you restore factory 
defaults for all parameters, these settings will not change.
“C” Function
Run 
Mode
Edit
Lo Hi
Defaults
Units
SRW Display
Func.
Code
Name
Description
–FE
(CE)
–FU
(UL)
–FR
(Jpn)
C081
[O] input span calibra-
tion
Range is 0 to 65530
✔ ✔
Factory-calibrated
>C081 O-ADJUST
TOP        02119
C082
[OI] input span calibra-
tion
Range is 0 to 65530
✔ ✔
Factory-calibrated
>C082 OI-ADJUST
TOP        02512
C083
[O2] input span calibra-
tion
Range is 0 to 65530
✔ ✔
Factory-calibrated
>C083 O2-ADJUST
TOP        02818
C085
Thermistor input tuning
Range is 0.0 to 1000
✔ ✔
105.0
105.0
105.0
>C085 THERM
ADJUST    0105.0
C086
[AM] terminal offset 
tuning
Range is 0.0 to 10.0V
✔ ✔
0.0
0.0
0.0
V
>C086 AM-MONITOR
OFFSET     00.0V
C087
[AMI] terminal meter 
tuning
Range is 0.0 to 250%
✔ ✔
80.
80.
80.
%
>C087 AMI-MON
ADJUST       080
C088
[AMI] terminal offset 
tuning
Range is 0 to 20mA
✔ ✔
Factory-calibrated
mA
>C088 AMI-MON
OFFSET    04.0mA
C121
[O] input zero calibra-
tion
Range is 0 to 6553 (65530)
✔ ✔
Factory-calibrated
>C121 O-ADJUST
ZERO       00000
C122
[OI] input zero calibra-
tion
Range is 0 to 6553 (65530)
✔ ✔
Factory-calibrated
>C122 OI-ADJUST
ZERO       00000
C123
[O2] input zero calibra-
tion
Range is 0 to 6553 (65530)
✔ ✔
Factory-calibrated
>C123 O2-ADJUST
ZERO       03622