Miscellaneous 
Functions
The following table contains miscellaneous functions not in other function groups.
C102/C103: Reset Mode / Restart Mode – The reset mode selection, set via parameter C102, 
determines how the inverter responds to the [RS] intelligent input signal or keypad Stop/Reset 
key in a trip condition. The options allow you to cancel the trip on either the OFF-to-ON or 
ON-to-OFF transition of [RS], and if desired, stop the inverter if it is in Run Mode. A trip event 
causes the inverter output to the motor to turn OFF immediately. If in Run Mode when the trip 
occurred, the inverter and motor will enter free-run stop (coasting) operation. In some applica-
tions, the motor and load will still be coasting when the inverter returns to normal Run Mode 
operation. For that situation, you can configure the inverter output (C103=00) to resume opera-
tion from 0 Hz and accelerate normally. Or, you can configure the inverter (C103=01) to 
resume operation from the current speed of the motor (frequency matching)—often used in 
applications such as HVAC.
“C” Function
Run 
Mode
Edit
Lo Hi
Defaults
Units
SRW Display
Func.
Code
Name
Description
–FE
(CE)
–FU
(UL)
–FR
(Jpn)
C091
Debug mode enable
Two option codes:
00 Display
01 No display
✘ ✔
00
00
00
>C091 INITIAL
DEBG         OFF
C101
Up/Down memory 
mode selection
Controls speed setpoint for 
the inverter after power 
cycle. Two option codes:
00 Clear last frequency 
(return to default 
frequency F001)
01 Keep last frequency 
adjusted by UP/DWN
✘ ✔
00
00
00
>C101 UP/DWN
DATA      NO-STR
“C” Function
Run 
Mode
Edit
Lo Hi
Defaults
Units
SRW Display
Func.
Code
Name
Description
–FE
(CE)
–FU
(UL)
–FR
(Jpn)
C102
Reset mode selection
Determines response to 
Reset input [RST].
Three option codes:
00 Cancel trip state at input 
signal ON transition, 
Stops inverter if in Run 
Mode
01 Cancel trip state at signal 
OFF transition, Stops 
inverter if in Run Mode
02 Cancel trip state at input 
signal ON transition, no 
effect if in Run Mode.
✔ ✔
00
00
00
>C102 RESET
SELECT       ON
C103
Restart mode after reset
Two option codes:
00 Restart at 0 Hz
01 Resume operation after 
frequency matching
✘ ✔
00
00
00
>C103 RESET
f-Mode       ZST
C111
Overload setting (2)
Range is 0.00 times rated 
current to 2.00 times rated 
current
✘ ✔
Rated current for 
each inverter model
A
>C111         OL
LEVEL2   0016.5A