Hitachi SJ300-037HFE 사용자 설명서

다운로드
페이지 289
Using Intelligent Input Terminals
Oper
ations
a
nd Moni
tor
ing
4–16
Jogging 
Command
The Jog input [JG] is used to command the 
motor to rotate slowly in small increments 
for manual operation. The speed is limited 
to 10 Hz. The frequency for the jogging 
operation is set by parameter A038. Jogging 
does not use an acceleration ramp. There-
fore setting the jogging frequency A038 too 
high will cause inverter tripping.
A jog command may arrive while the motor 
is running. You can program the inverter to 
either ignore or respond to a jog command 
in this case by using function A039. The 
type of deceleration used to end a motor jog 
is also selectable by programming function A039. Six jog mode options are defined below:
In the left example diagram below, the Jog command is ignored. In the right example diagram, 
a jog command interrupts a Run mode operation. However, if the Jog command turns ON 
before the [FW] or [RV] terminal turns ON, the inverter output turns OFF.
Jogging During Motor Operation
Jog Deceleration Method
Disabled, A039=
Enabled, A039=
00
03
Free-run stop (coasting)
01
04
Deceleration (normal level) and stop
02
05
Use DC braking and stop
Opt.
Code
Symbol
Function Name
Input 
State
Description
06
JG
Jogging
ON
Enters Jog Mode if enabled (see above)
OFF
Jog is OFF
Valid for 
inputs:
C001, C002, C003, C004, 
C005, C006, C007, C008
Required 
settings:
A002= 01, A038 > B082, 
A038 > 0, A039=00 to 05
Notes: 
• 
Jogging is not performed when the value of 
A038 jogging frequency is smaller than the 
start frequency B082 or the
 
value is 0 Hz.
• Be sure to turn ON [FW] or [RV] after the 
[JG] input turns ON for a jog operation.
• When setting A039 to 02 or 05, you must also 
set the DC braking parameters.
[JG]
[FW]
Jog decel type
[RV]
Output
frequency
A038
A039
t
[JG]
[FW]
Output
frequency
A039=00, 01, 02
Decelerating stop (00) shown
[JG]
[FW]
Output
frequency
A039=03, 04, 05
Free-run stop (05) shown
A038
A038
t
t
5
3
1
7
6
4
2
8
FW
TH
PLC
CM1
P24
CM1
See I/O specs on page 
.
Example: (Default input configuration 
shown—see page 
. Jumper position 
shown is for –xFU/-xFR models; for –xFE 
models, see page 
.)
JG