Using Intelligent Input Terminals
Oper
ations
a
nd Moni
tor
ing
4–24
In the previous timing diagram, when the motor has been started across the line, Mg2 is 
switched OFF and Mg3 is switched ON. With the Forward command to the inverter already 
ON, the [CS] terminal is switched ON and relay Mg1 contacts close. The inverter will then read 
the motor RPM (frequency matching). When the [CS] terminal is switched OFF, the inverter 
applies the Retry wait time before motor restart parameter (B003).
Once the delay time has elapsed the inverter will then start and match the frequency (if greater 
than the threshold set by B007). If the ground fault interrupter breaker (GFI) trips on a ground 
fault, the bypass circuit will not operate the motor. When an inverter backup is required, take 
the supply from the bypass circuit GFI. Use control relays for [FW], [RV], and [CS].
The commercial power source switching function requires you to assign [CS] to an intelligent 
input terminal, using option code 14.
Opt.
Code
Symbol
Function Name
Input 
State
Description
14
CS
Commercial Power 
Change
ON
OFF-to-ON transition signals the inverter 
that the motor is already running at 
powerup (via bypass), thus suppressing 
the inverter’s motor output in Run Mode
OFF
ON-to-OFF transition signals the inverter 
to apply a time delay (B003), frequency 
match its output to existing motor speed, 
and resume normal Run Mode operation
Valid for inputs:
C001, C002, C003, C004, 
C005, C006, C007, C008
Required 
settings:
B003, B007
Notes: 
• 
If an over-current trip occurs during frequency 
matching, extend the retry wait time B003.
5
3
1
7
6
4
2
8
FW
TH
PLC
CM1
P24
CM1
See I/O specs on page 
Example: (Requires input configuration—
see page 
. Jumper position shown is 
for –xFU/-xFR models; for –xFE models, 
see page 
.)
CS