Hitachi SJ300-037HFE 사용자 설명서

다운로드
페이지 289
SJ300 Inverter
Oper
ati
ons
and Monitor
ing
4–25
Software Lock
When the terminal [SFT] is turned ON, the data of all the parameters and functions (except the 
output frequency, depending on the setting of B031) is locked (prohibited from editing). When 
the data is locked, the keypad keys cannot edit inverter parameters. To edit parameters again, 
turn OFF the [SFT] terminal input.
Use parameter B031 to select whether the output frequency is excluded from the lock state or is 
locked as well.
Opt.
Code
Symbol
Function Name
Input 
State
Description
15
SFT
Software Lock
ON
The keypad and remote programming 
devices are prevented from changing 
parameters
OFF
The parameters may be edited and stored
Valid for 
inputs:
C001, C002, C003, C004, 
C005, C006, C007, C008
Required 
settings:
B031 (excluded from lock)
Notes: 
• 
When the [SFT] terminal is turned ON, only 
the output frequency can be changed.
• Software lock can include the output 
frequency by setting B031.
• Software lock by the operator is also possible 
without the [SFT] terminal being used 
(B031).