Three-wire
Interface
Operation
The 3-wire interface is an industry standard motor control interface. This function uses two 
inputs for momentary contact start/stop control, and a third for selecting forward or reverse 
direction. To implement the 3-wire interface, assign 20 [STA] (Start), 21 [STP] (Stop), and 22 
[F/R] (Forward/Reverse) to three of the intelligent input terminals. Use momentary contact for 
Start and Stop. Use a selector switch, such as SPST for the Forward/Reverse input. Be sure to 
set the operation command selection A002=01 for input terminal control of motor.
If you have a motor control interface that needs logic-level control (rather than momentary 
pulse control), use the [FW] and [RV] inputs instead.
The diagram below shows the use of 3-wire control. STA (Start Motor) is an edge-sensitive 
input; an OFF-to-ON transition gives the Start command. The control of direction is level-
sensitive, and the direction may be changed at any time. STP (Stop Motor) is also a level-
sensitive input.
Opt.
Code
Symbol
Function Name
Input 
State
Description
20
STA
Start Motor
ON
Start motor rotation on momentary 
contact (uses acceleration profile)
OFF
No change to motor operation
21
STP
Stop Motor
ON
No change to motor operation
OFF
Stop motor rotation on momentary contact 
(uses deceleration profile)
22
F/R
Forward/Reverse
ON
Select reverse direction of rotation
OFF
Select forward direction of rotation
Valid for 
inputs:
C001, C002, C003, C004, 
C005, C006, C007, C008
Required 
settings:
A002=01
Notes: 
• 
The STP logic is inverted. Normally the 
switch will be closed, so you open the switch 
to stop. In this way, a broken wire causes the 
motor to stop automatically (safe design).
• When you configure the inverter for 3-wire 
interface control, the dedicated [FW] terminal 
is automatically disabled. The [RV] intelligent 
terminal assignment is also disabled.
5
3
1
7
6
4
2
8
FW
TH
PLC
CM1
P24
CM1
See I/O specs on page 
Example: (Requires input configuration—
see page 
. Jumper position shown is 
for –xFU/-xFR models; for –xFE models, 
see page 
.)
F/R
STA
STP
[STA] terminal
[F/R] terminal
[STP] terminal
Motor revolution speed
Forward
Reverse
t