Reset Inverter
The [RS] terminal causes the inverter to 
execute the reset operation. If the inverter is 
in Trip Mode, the reset cancels the Trip 
state. When the signal [RS] is turned ON 
and OFF, the inverter executes the reset 
operation. The minimum pulse width for 
[RS] must be 12 ms or greater. The alarm 
output will be cleared within 30 ms after the 
onset of the Reset command.
WARNING: After the Reset command is given and the alarm reset occurs, the motor will 
restart suddenly if the Run command is already active. Be sure to set the alarm reset after 
verifying that the Run command is OFF to prevent injury to personnel.
Opt.
Code
Symbol
Function Name
Input 
State
Description
18
RS
Reset Inverter
ON
The motor output is turned OFF, the Trip 
Mode is cleared (if it exists), and powerup 
reset is applied
OFF
Normal power-on operation
Valid for 
inputs:
C001, C002, C003, C004, 
C005, C006, C007, C008
Required 
settings:
B003, B007, C102, C103
Notes: 
• 
When the control terminal [RS] input is 
already ON at powerup for more than 4 
seconds, the remote operator display is “R-
ERROR COMM<2>” (the display of the 
digital operator is –  –  –  –). However, the 
inverter has no error. To clear the digital 
operator error, turn OFF the terminal [RS] 
input and press one of the operator keys.
• The active edge (leading or trailing) of the [RS] signal is determined by the setting of 
C102.
• A terminal configured with the [RS] function can only be configured as a normally open 
contact. The terminal cannot be used in the normally closed contact state.
• When input power is turned ON, the inverter performs the same reset operation as it does 
when a pulse on the [RS] terminal occurs.
[RS]
Alarm  output
t
12 ms
minimum
approx. 30 ms
5
3
1
7
6
4
2
8
FW
TH
PLC
CM1
P24
CM1
See I/O specs on page 
Example: (Default input configuration 
shown—see page 
. Jumper position 
shown is for –xFU/-xFR models; for –xFE 
models, see page 
.)
RS