SJ300 Inverter
Oper
ati
ons
and Monitor
ing
4–33
Remote Control 
Up and Down 
Functions
The [UP] [DWN] terminal functions can adjust the output frequency for remote control while 
the motor is running. The acceleration time and deceleration time used with this function is the 
same as for normal operation ACC1 and DEC1 (2ACC1,2DEC1). The input terminals operate 
as follows:
• Acceleration - When the [UP] contact is turned ON, the output frequency accelerates from 
the current value. When it is turned OFF, the output frequency maintains its current value.
• Deceleration - When the [DWN] contact is turned ON, the output frequency decelerates 
from the current value. When it is turned OFF, the output frequency maintains its current 
value.
In the graph below, the [UP] and [DWN] terminals activate while the Run command remains 
ON. The output frequency responds to the [UP] and [DWN] commands. 
It is possible for the inverter to retain the frequency set from the [UP] and [DWN] terminals 
through a power loss. Parameter C101 enables/disables the memory. If disabled, the inverter 
retains the last frequency before an UP/DWN adjustment. Use the [UDC] terminal to clear the 
memory and return to the original set output frequency.
Opt.
Code
Symbol
Function Name
Input 
State
Description
27
UP
Remote Control 
UP Function
ON
Accelerates (increases output frequency) 
motor from current frequency
OFF
Output to motor operates normally
28
DWN
Remote Control 
DOWN Function
ON
Decelerates (decreases output frequency)
 
motor from current frequency
OFF
Output to motor operates normally
29
UDC
Remote Control 
Data Clear
ON
Clears the Up/down frequency memory
OFF
No effect on Up/down memory
Valid for inputs:
C001, C002, C003, C004, 
C005, C006, C007, C008
Required 
settings:
A001 = 02
C101 = 01 (enables memory)
Notes: 
• 
This feature is available only when the 
frequency command source is programmed 
for operator control. Confirm A001 is set to 
02.
• This function is not available when [JG] is in 
use.
• The range of output frequency is 0 Hz to the 
value in A004 (maximum frequency setting).
• The Remote Control Up/Down function 
varies the inverter speed by directly writing to 
the F001 output frequency setting.
Output
frequency
[UP]
[FW, RV]
[DWN]
t
5
3
1
7
6
4
2
8
FW
TH
PLC
CM1
P24
CM1
See I/O specs on page 
Example: (Requires input configuration—
see page 
. Jumper position shown is 
for –xFU/-xFR models; for –xFE models, 
see page 
.)
UDC DWN
UP