SJ300 Inverter
Oper
ati
ons
and Monitor
ing
4–35
Overload
Restriction
The inverter constantly monitors the motor current during acceleration, deceleration, and 
constant speed. If the inverter reaches the overload restriction level, it adjusts the output 
frequency automatically to limit the amount of overload. This function prevents an over-current 
trip by inertia during rapid acceleration or large changes in load at constant speed. It also 
attempts to prevent an over-voltage trip on deceleration due to regeneration. It accomplishes 
this by temporarily suspending deceleration and/or increasing the frequency in order to dissi-
pate regenerative energy. Once the DC bus voltage falls sufficiently, deceleration will resume.
OLR Parameter Selection – Two sets of overload restriction parameter settings and values are 
available as outlined in the table below. Use the B021—B026 group of settings to configure the 
two set of parameters as needed. By assigning the Overload Restriction function [OLR] to an 
intelligent terminal, you can select the set of restriction parameters that is in effect.   
Function
Function Code
Data or Range
Description
Set 1
Set 2
Overload Restriction 
Operation Mode
B021
B024
00
Disable
01
Enabled during accel 
and constant speed
02
Enabled during constant 
speed
03
Enabled during accel, 
constant speed, and 
decel
Overload Restriction 
Setting
B022
B025
Rated current * 0.5 
to rated current * 2
Current value at which 
the restriction begins
Deceleration Rate at 
Overload Restriction
B023
B026
0.1 to 30 seconds
Deceleration time when 
overload restriction 
operates
Opt.
Code
Symbol
Function Name
Input 
State
Description
39
OLR
Overload Restric-
tion Selection
ON
Selects Overload Restriction Set 2,
B024, B025, B026 settings in effect
OFF
Selects Overload Restriction Set 1,
B021, B022, B023 settings in effect
Valid for inputs:
C001, C002, C003, C004, 
C005, C006, C007, C008
Required 
settings:
B021, B022, B023 (Mode 1),
B024, B025, B026 (Mode 2)
Notes: 
• 
If the overload restriction constant (B023 or 
B026) is set too short, an over-voltage trip 
during deceleration will occur due to regener-
ative energy from the motor.
• When an overload restriction occurs during 
acceleration, the motor will take longer to 
reach the target frequency, or may not reach 
it. The inverter will make the following 
adjustments:
a) Increase the acceleration time
b) Raise torque boost
c) Raise overload restriction level
5
3
1
7
6
4
2
8
FW
TH
PLC
CM1
P24
CM1
See I/O specs on page 
Example: (Requires input configuration—
see page 
. Jumper position shown is 
for –xFU/-xFR models; for –xFE models, 
see page 
.)
OLR