Using Intelligent Input Terminals
Oper
ations
a
nd Moni
tor
ing
4–34
Force Operation 
from Digital 
Operator
This function permits a digital operator interface to override the Run command source setting 
(A002) when it is configured for a source other than the operator interface. When the [OPE] 
terminal is ON and the operator interface gives a Run command, the inverter uses the standard 
output frequency settings to operate the motor.
Opt.
Code
Symbol
Function Name
Input 
State
Description
31
OPE
Force Operation 
from Digital 
Operator
ON
Forces the operator interface Run 
command to over-ride commands from 
input terminals (such as [FW], [RV]).
OFF
Run command operates normally, as 
configured by A002
Valid for inputs:
C001, C002, C003, C004, 
C005, C006, C007, C008
Required 
settings:
A001
A002 (set not equal to 02)
Notes: 
• 
When changing the [OPE] state during Run 
Mode (inverter is driving the motor), the 
inverter will stop the motor before the new 
[OPE] state takes effect.
• If the [OPE] input turns ON and the digital 
operator gives a Run command while the 
inverter is already running, the inverter stops 
the motor. Then the digital operator can 
control the motor. 
5
3
1
7
6
4
2
8
FW
TH
PLC
CM1
P24
CM1
See I/O specs on page 
Example: (Requires input configuration—
see page 
. Jumper position shown is 
for –xFU/-xFR models; for –xFE models, 
see page 
.)
OPE