Using Intelligent Output Terminals
Oper
ations
a
nd Moni
tor
ing
4–44
Frequency Arrival 
Signals
The Frequency Arrival group of outputs help coordinate external systems with the current 
velocity profile of the inverter. As the name implies, output [FA1] turns ON when the output 
frequency arrives at the standard set frequency (parameter F001). Outputs [FA2] through [FA5] 
provide variations on this function for increased flexibility, relying on two programmable accel/ 
decel thresholds. For example, you can have an output turn ON at one frequency during accel-
eration, and have it turn OFF at a different frequency during deceleration. All transitions have 
hysteresis to avoid output chatter if the output frequency is near one of the thresholds. 
Opt.
Code
Symbol
Function Name
Output 
State
Description
01
FA1
Frequency arrival 
type 1 – constant 
speed
ON
when output to motor is at the standard set 
frequency F001
OFF
when output to motor is not at the set 
frequency F001
02
FA2
Frequency arrival 
type 2 – over-
frequency
ON
when output to motor is at or above the FA 
threshold 1(C042) during accel
OFF
when the output to motor is below the FA 
threshold 1 (C043) during decel
06
FA3
Frequency arrival 
type 3 – at 
frequency
ON
when output to motor is at the FA thresh-
old 1 (C042) during accel, or at C043 
during decel
OFF
when the output to motor is not at either 
the FA threshold 1 (C042) during accel or 
at C43 during decel
24
FA4
Frequency arrival 
type 4 – over-
frequency (2)
ON
when output to motor is at or above the FA 
threshold 2 (C045) during accel
OFF
when the output to motor is below the FA 
threshold 2 (C046) during decel
25
FA5
Frequency arrival 
type 5 – 
at frequency (2)
ON
when output to motor is at the FA thresh-
old 2 (C045) during accel, or at C046 
during decel
OFF
when the output to motor is not at either 
the FA threshold 2 (C045) during accel or 
at C046 during decel
Valid for 
outputs:
11, 12, 13, 14, 15,
AL0 – AL2
Required 
settings:
F001, for FA1
C042 & C043, for FA2 & FA3
C045 & C046, for FA4 & FA5
Notes: 
• 
For most applications you will need to use 
only one or two of the frequency arrival type 
outputs (see example). However, it is possible 
assign all five output terminals to output 
functions [FA1] through [FA5].
• For each frequency arrival threshold, the 
output anticipates the threshold (turns ON 
early) by an amount equal to 1% of the 
maximum frequency set for the inverter.
• The output turns OFF as the output frequency 
moves away from the threshold, delayed by 
an amount equal to 2% of the max. frequency.
+
RY
See I/O specs on page 
.
Inverter output 
terminal circuit
CM2
13
14
15
11
12
Example: (Default output configuration 
shown—see page 
.)
FA1