Analog Output Operation
In the system design for inverter applications it is sometimes useful to monitor inverter opera-
tion from a remote location. In some cases, this requires only a panel-mounted analog meter 
(moving-coil type). In other cases, a controller device such as a PLC may monitor and 
command the inverter frequency and other functions. The inverter can transmit the (real-time) 
output frequency, current, torque, or other parameters to the controller to confirm actual opera-
tion. The monitor output terminal [FM] serves these purposes.
[FM] Terminal
The inverter provides an analog/digital output on 
terminal [FM] (frequency monitor). It uses 
terminal [CM1] as digital GND reference. While 
many applications use this terminal to monitor 
the output frequency, you can configure terminal 
[FM] to transmit one of several parameters. 
Most use pulse-width modulation (PWM) to 
represent the value, while one parameter uses 
frequency modulation (FM) to represent the 
value. Do not confuse the notation for terminal 
[FM] (with brackets) with FM signal type.
The following table lists the configurations for terminal [FM]. Use function C027 to configure.
Note 1: Display substitutes only during sensorless vector control, 0Hz domain sensorless 
vector control, and vector control
PWM Signal Type
The pulse-width modulated signal at terminal 
[FM] is primarily designed for driving a moving-
coil meter. The pulse-width modulated signal is 
automatically averaged by the inertia of the 
moving-coil mechanism—converting the PWM 
signal to an analog representation. Be sure to use 
a 10V full-scale DC voltmeter.
The signal characteristics of terminal [FM] in 
PWM signal configuration is shown below
Func.
Code
Description
Waveform
Full Scale Value
C027
00
Output frequency
PWM
0 – Max. frequency (Hz)
01
Output current
PWM
0 – 200%
02
Output torque *1
PWM
0 – 200%
03
Output frequency
FM
0 – Max. frequency (Hz)
04
Output voltage
PWM
0 – 100%
05
Input electric power
PWM
0 – 200%
06
Thermal load ratio
PWM
0 – 100%
07
LAD frequency
PWM
0 – Max. frequency (Hz)
D GND
Analog/digital Output
See I/O specs on page 
H O2
FM
AM
O
OI
L
FW
TH
PLC
P24
CM1
AMI
H O2
FM
AM
O
OI
L
FW
TH
PLC
P24
CM1
AMI
+
0 to 10V,
1 mA
[FM]
[FM] output value
t
T
---
=
Period T = 6.4ms constant (156 Hz)
Selects FM type output
= [FM] terminal 8-bit gain setting
B081
C27=00, 01, 02, 04, 05, 06, 07
t
10V
0V
t
T