Analog Output Operation
Oper
ations
a
nd Moni
tor
ing
4–64
[AM] and [AMI] 
Terminals
The [AM] and [AMI] terminals provide signals 
to monitor various inverter parameters such as 
output frequency, output current, and torque. 
The terminals provide these analog signal types:
• [AM] terminal: 0–10V analog output signal
• [AMI] terminal: 4–20mA analog output 
signal
These signals both use the [L] terminal for signal 
return. Eight different inverter parameters may 
be monitored independently at either the [AM] 
or [AMI] terminal, as listed in the table below. 
Use C028 to configure terminal [AM], and C029 
to configure terminal [AMI].
Note 1: Display of torque is possible only during sensorless vector control, 0Hz domain 
sensorless vector control, and vector control with feedback
The analog signals may need some adjustment for gain or offset to compensate for variances in 
the system. For example, the signals may drive a panel meter and require a full-scale gain 
adjustment. The table below lists the function codes and their descriptions. The [AM] and 
[AMI] terminals have separate gain and offset adjustments. Note the default values. 
Func.
Terminal
Code
Description
Full Scale Value
C028 / 
C029
[AM] / 
[AMI]
00
Output frequency
0 – Max. frequency (Hz)
01
Output current
0 – 200%
02
Output torque *1
0 – 200%
04
Output voltage
0 – 100%
05
Input electric power
0 – 200%
06
Thermal load ratio
0 – 100%
07
LAD frequency
0 – Max. frequency (Hz)
Func.
Terminal
Description
Range
Default
B080
[AM]
Gain adjustment
0 – 255
180
C086
[AM]
Offset Adjustment
0.0 – 10.0V
0.0V
C087
[AMI]
Gain adjustment
0 – 255
80
C088
[AMI]
Offset Adjustment
0.0 – 20.0mA
0.0mA
H O2
FM
AM
O
OI
L
AMI
A GND
See I/O specs on page 
0–10V analog output
4–20mA analog output