SJ300 Inverter
Oper
ati
ons
and Monitor
ing
4–63
To calibrate the meter reading, generate a full-scale output (always ON) at terminal [FM]. Then 
use parameter B081(gain setting from 0 to 255) to adjust the corresponding full-scale reading 
of the meter. For example, when the inverter output frequency is 60 Hz, change the value of 
B081 so that the meter reads 60 Hz.
TIP: When using the analog meter for monitoring, adjust the meter so it has a zero reading 
when the [FM] output is zero. Then use scale factor B081 to adjust the [FM] output so the 
maximum frequency in the inverter corresponds to a full-scale reading on the meter.
NOTE: The indicator accuracy after adjustment is about 
±5%. Depending on the motor, the 
accuracy may exceed this value.
PWM Smoothing Circuit – Note that 
standard analog output signals are avail-
able on terminals [AM] and [AMI], 
covered in the next section. However, you 
may also wish to smooth the PWM signal 
at the [FM] terminal and convert it to an 
analog signal. The [FM] terminal will then 
generate a relatively stable DC analog 
voltage that represents the output value. 
To do this, use the circuit shown to the 
right. Note the output impedance of the 
circuit is at least 82k
Ω, so the monitoring 
device needs an input impedance of 1M
Ω 
or greater. Otherwise, the impedance of 
the smoothing circuit will cause a non-
linearity in the reading.
FM Signal Type
The frequency-modulated output at terminal [FM] varies its frequency with the inverter output 
frequency (when C027=03). This frequency is digitally controlled for accuracy, and does not 
use the B081 gain setting when C027=03 (frequency modulation). 
H O2
FM
AM
O
OI
L
FW
TH
PLC
P24
CM1
AMI
+
+
+
33k
Ω
82k
Ω
Volts
1
µF
T
1
[FM] Output Frequency
---------------------------------------------------------
=
Selects FM type output
[FM]
T
[FM] Output Frequency
1
T
---
=
C027=03
t
10V
0V
50% fixed duty cycle