Hitachi SJ300-037HFE 사용자 설명서

다운로드
페이지 289
SJ300 Inverter
In
v
e
rt
er Mounting
and In
stallati
on
2–13
Step 5: The wiring enters the inverter through 
the entry/exit plate as shown to the right. The 
rubber grommets have a solid, thin membrane, 
so that unused ones continue to seal the opening. 
To create an opening, use a sharp knife and 
carefully cut an “X” in the center of the 
grommet as shown. Be especially careful to 
avoid cutting into the thick outer ring, so that the 
wiring will have a cushion from contacting the 
metal plate.
NOTE: Some inverter models will have a 
wiring box for NEMA rating compliance. Make 
sure the wire entry to the NEMA box also has 
protective cushion from chaffing of insulation.
 Before proceeding, please study the caution and warning messages below.
WARNING:  “Use 60/75°C Cu wire only” or equivalent.
WARNING: “Open Type Equipment.” For models SJ300–750H to SJ300–1500H.
WARNING: “A Class 2 circuit wired with Class 1 wire” or equivalent.
WARNING: “Suitable for use on a circuit capable of delivering not more than 10,000 rms 
symmetrical amperes, 240 V maximum.” For models with suffix L.
WARNING: “Suitable for use on a circuit capable of delivering not more than 10,000 rms 
symmetrical amperes, 480 V maximum.” For models with suffix H.
HIGH VOLTAGE: Be sure to ground the unit. Otherwise, there is a danger of electric shock 
and/or fire.
HIGH VOLTAGE: Wiring work shall be carried out only by qualified personnel. Otherwise, 
there is a danger of electric shock and/or fire.
HIGH VOLTAGE: Implement wiring after checking that the power supply is OFF. Otherwise, 
you may incur electric shock and/or fire.
HIGH VOLTAGE: Do not connect wiring to an inverter or operate an inverter that is not 
mounted according the instructions given in this manual. Otherwise, there is a danger of elec-
tric shock and/or injury to personnel.
5
Prepare for 
Wiring
Cut grommet(s) for 
use as shown