Determining wire and fuse sizes, continued...
Note 1: Field wiring must be made by a UL-listed and CSA certified ring lug terminal 
connector sized for the wire gauge involved. The connector must be fixed by using 
the crimping tool specified by the connector manufacturer.
Note 2: Be sure to consider the capacity of the circuit breaker to be used.
Note 3: Be sure to use a larger wire gauge if power line length exceeds 66 ft (20m).
Motor 
Output
400V
Inverter 
Models
Wiring *1
Power Lines *3
Chassis Ground
Brake Res.
HP
kW
AWG
mm
2
Fuse
(UL-
rated, 
class J,
600V)
Breaker
( GFI 
type) *2
AWG, 
rec.
AWG, 
UL
mm
2
AWG
mm
2
1
0.75
SJ300–007HFU/E
20
1.25
10A
5A
16
14
1.25
20
1.25
2
1.5
SJ300–015HFU/E
18
2
10A
10A
16
14
1.25
18
2
3
2.2
SJ300–022HFU/E
16
2
10A
10A
16
14
1.25
16
2
5
4.0
SJ300–040HFU/E
14
2
15A
15A
16
14
1.25
14
2
7.5
5.5
SJ300–055HFU/E
12
2
15A
30A
14
14
2
12
2
10
7.5
SJ300–075HFU/E
10
3.5
20A
30A
10
12
3.5
10
3.5
15
11
SJ300–110HFU/E
8
5.5
30A
50A
8
10
5.5
8
5.5
20
15
SJ300–150HFU/E
6
8
40A
60A
8
10
8
25
18.5
SJ300–185HFU/E
6
14
50A
60A
4
10
14
30
22
SJ300–220HFU/E
4
14
60A
75A
4
10
14
40
30
SJ300–300HFU/E
3
22
70A
100A
3
10
22
50
37
SJ300–370HFU/E
4 || 4
14 || 14
90A
100A
3
8
22
60
45
SJ300–450HFU/E
1 (75°C)
38
125A
150A
1
8
22
75
55
SJ300–550HFU/E
2 || 2
22 || 22
125A
175A
1
6
30
100
75
SJ300–750HFU/E
1 || 1 
(75°C)
30 || 30
175A
225A
1/0
6
50
125
90
SJ300–900HFU/E
1 || 1 
(75°C)
38 || 38
200A
225A
3/0
6
80
150
110
SJ300–1100HFU/E
1/0 || 1/0
50 || 50
250A
350A
3/0
4
80
175
132
SJ300–1320HFE
3/0 || 3/0
80 || 80
300A
350A
4/0
4
100
200
150
SJ300–1500HFU
3/0 || 3/0
80 || 80
300A
350A
4/0
4
100