Hitachi SJ300-037HFE 사용자 설명서

다운로드
페이지 289
Step-by-Step Basic Installation
In
v
e
rt
er Moun
ting
and Install
a
tion
2–14
Determining Wire 
and Fuse Sizes
This section includes tables for 200V class and 400V class inverters (on the next page). The 
following notes will help you read the tables in this section:
• Locate the row corresponding to the motor size and particular inverter in your application. 
The maximum motor current determines the recommended wire sizes.
• The length column specifies that some inverters can optionally use a smaller wire gauge if 
the wires are shorter than 10m and the inverter is located in an enclosure.
• Power Lines columns include wires connecting to terminals [R, S, T, U, V, W, P, PD, and N]. 
Only power input and motor leads will be fused: [R, S, T, U, V, and W]. The breaker ratings 
(GFI—ground fault interrupter) are slightly higher than fuse ratings to allow for nominal 
surges without tripping.
• The chassis ground columns list the Hitachi-recommended AWG and the minimal AWG for 
UL conformity.
• The optional external braking resistor wiring only applies to a few models that have a built-
in braking unit. The other models use an optional external braking unit.
• Parallel wires increase effective wire gauge, and are denoted by “||” in the tables.
• Signal Lines, not listed in these tables, connect to the removable logic connector. The recom-
mended wire gauge for all wiring to the logic connector is 28 AWG (0.75 mm
2
). Be sure to 
use shielded wire for any analog signals.
* See notes for wiring tables on the following page.
Motor 
Output
200V
Inverter 
Models
Wiring *1
Power Lines *3
Chassis Ground
Brake Res.
HP
kW
AWG
mm
2
Fuse
(UL-
rated, 
class J,
600V)
Breaker 
(GFI 
type) *2
AWG, 
rec.
AWG, 
UL
mm
2
AWG
mm
2
1/2
0.4
SJ300–004LFU
20
1.25
10A
5A
16
14
1.25
20
1.25
1
0.75
SJ300–007LFU
18
1.25
10A
10A
16
14
1.25
18
1.25
2
1.5
SJ300–015LFU
14
2
10A
15A
16
14
1.25
14
2
3
2.2
SJ300–022LFU
14
2
15A
20A
16
14
1.25
14
2
5
3.7
SJ300–037LFU
10
3.5
20A
30A
10
12
3.5
10
3.5
7.5
5.5
SJ300–055LFU
8
5.5
30A
50A
8
10
5.5
8
5.5
10
7.5
SJ300–075LFU
6
8
40A
60A
8
10
8
8
5.5
15
11
SJ300–110LFU
4
14
60A
75A
4
10
14
8
5.5
20
15
SJ300–150LFU
2
22
80A
100A
3
8
22
25
18.5
SJ300–185LFU
4 || 4
14 || 14
100A
100A
3
8
22
30
22
SJ300–220LFU
4 || 4
14 || 14
125A
150A
2
8
30
40
30
SJ300–300LFU
2 || 2
22 || 22
150A
200A
2
6
30
50
37
SJ300–370LFU
2 || 2
30 || 30
175A
225A
1/0
6
38
60
45
SJ300–450LFU
1 || 1 
(75°C)
38 || 38
225A
225A
3/0
6
38
75
55
SJ300–550LFU
2/0 || 2/0
60 || 60
250A
350A
3/0
4
60