“B” Group: Fine-Tuning Functions
Configur
ing Dr
iv
P
a
ra
meters
3–30
CAUTION: When a loss of phase occurs, increased ripple current will markedly reduce main 
capacitor life over time. Diode bridge failure can also result. If phase loss occurs under load, 
the inverter could be damaged. Please pay particular attention to the setting of function B006.
Electronic 
Thermal Overload 
Alarm Setting
The thermal overload detection protects 
the inverter and motor from overheating 
due to an excessive load. It uses a current/
inverse time curve to determine the trip 
point. The thermal overload alarm [THM] 
is the resulting intelligent output.
First, use B013 to select the torque 
characteristic that matches your load. 
This allows the inverter to utilize the best 
thermal overload characteristic for your 
application.
B002
Allowable under-
voltage power failure 
time
The amount of time a power 
input under-voltage can 
occur without tripping the 
power failure alarm. If 
under-voltage exists longer 
than this time, the inverter 
trips, even if the restart 
mode is selected. If it exists 
less than this time retry will 
be attempted. Range is 0.3 to 
1.0 sec.
✘ ✔
1.0
1.0
1.0
sec.
>b002 IPS
TIME        1.0s
B003
Retry wait time before 
motor restart
Time delay after a trip 
condition goes away before 
the inverter restarts the 
motor.
Range is 0.3 to 100 seconds.
✘ ✔
1.0
1.0
1.0
sec.
>b003 IPS
WAIT      001.0s
B004
Instantaneous power 
failure / under-voltage 
trip alarm enable
Three option codes:
00 Disable
01 Enable
02 Disable during stop and 
ramp to stop
✘ ✔
00
00
00
>b004 IPS
TRIP        OFF
B005
Number of restarts on 
power failure / under-
voltage trip events
Two option codes:
00 Restart 16 times
01 Always restart
✘ ✔
00
00
00
>b005 IPS
RETRY       16
B006
Phase loss detection 
enable
Two option codes:
00 Disable – no trip on 
phase loss
01 Enable – trip on phase 
loss
✘ ✔
00
00
00
>b006 PH-FAIL
SELECT       OFF
B007
Restart frequency 
threshold
When the frequency of the 
motor is less than this value, 
the inverter will restart at 
0 Hz.
Range is 0.00 to 400.0 Hz
✘ ✔ 0.00 0.00 0.00
Hz
>b007 IPS
F      0000.00Hz
“B” Function
Run 
Mode
Edit
Lo Hi
Defaults
Units
SRW Display
Func.
Code
Name
Description
–FE
(CE)
–FU
(UL)
–FR
(Jpn)
Output frequency
Constant torque
Reduced
torque
B013=01
B013=00
Trip current 
reduction 
factor
x 1.0
x 0.8
x 0.6
0
5
20
60
120
Hz