Reset Inverter 
The [RS] terminal causes the inverter to execute 
the reset operation. If the inverter is in Trip Mode, 
the reset cancels the Trip state. When the signal 
[RS] is turned ON and OFF, the inverter executes 
the reset operation. The minimum pulse width for 
[RS] must be 12 ms or greater. The alarm output 
will be cleared within 30 ms after the onset of the 
Reset command. 
 
WARNING: After the Reset command is given and the alarm reset occurs, the motor will 
restart suddenly if the Run command is already active. Be sure to set the alarm reset after 
verifying that the Run command is OFF to prevent injury to personnel. 
 
Option 
Code 
Terminal 
Symbol 
Function Name 
State
Description 
ON 
The motor output is turned OFF, the Trip Mode is 
cleared (if it exists), and powerup reset is applied 
18 
RS Reset 
Inverter 
OFF
Normal power ON operation 
Valid for inputs: 
C001
~
C007
 
Required settings  (none) 
Notes: 
•  While the control terminal [RS] input is ON, the 
keypad displays alternating segments. After RS 
turns OFF, the display recovers automatically. 
•  Pressing the Stop/Reset key of the digital operator 
can generate a reset operation only when an 
alarm occurs. 
Example (default input configuration shown see 
page 66
): 
 
 
 
 
 
 
 
See I/O specs on 
page 21,22.
 
•  A terminal configured with the [RS] function can only be configured for normally open operation. The 
terminal cannot be used in the normally closed contact state. 
•  When input power is turned ON, the inverter performs the same reset operation as it does when a pulse 
on the [RS] terminal occurs. 
•  The Stop/Reset key on the inverter is only operational for a few seconds after inverter powerup when a 
hand-held remote operator is connected to the inverter. 
•  If the [RS] terminal is turned ON while the motor is running, the motor will be free running (coasting). 
•  If you are using the output terminal OFF delay feature (any of 
C145
C147
C149
 > 0.0 sec.), the [RS] 
terminal affects the ON-to-OFF transition slightly. Normally (without using OFF delays), the [RS] input 
causes the motor output and the logic outputs to turn OFF together, immediately. However, when any 
output uses an OFF delay, then after the [RS] input turns ON, that output will remain ON for an additional 
1 sec. period (approximate) before turning OFF. 
 
[RS]
1
0
t
Alarm
signal
1
0
Approx. 30 ms 
12 ms 
minimum 
RS
7
6
5
4
3
2
1
 
L
 
P24
 
PLC