Hitachi hitachi series inverter 사용자 설명서

다운로드
페이지 99
 
46 
Monitoring functions 
 
NOTE:. Mark “ ” in b031=10 shows the accessible parameters when b031 is set “10”, high 
level access. 
* Please change from"
04
 (Basic display)" to "
00
 (Full display)" in parameter 
   
B037
 (Function code display restriction), in case some parameters cannot be displayed.
   
 
IMPORTANT 
Please be sure to set the motor nameplate data into the appropriate parameters 
to ensure proper operation and protection of the motor: 
 
b012 is the motor overload protection value 
 
A082 is the motor voltage selection 
 
H003 is the motor kW capacity 
 
H004 is the number of motor poles 
Please refer to the appropriate pages in this guide and the Instruction Manual for further details. 
 
“d” Function 
Func. 
Code 
Name 
Description 
Run 
Mode 
Edit 
Units 
D001 
Output frequency monitor 
Real time display of output frequency 
to motor from 
0.0 to 400.0Hz 
If  b163 is set high, output frequency 
(F001) can be changed by up/down 
key with d001 monitoring. 
− 
Hz 
D002 
Output current monitor 
Filtered  display of output current to 
motor, range is 
0 to 655.3 ampere (~99.9 ampere for 
1.5kW and less) 
− 
D003 
Rotation direction monitor 
Three different indications: 
“F” 
…Forward 
“o” 
…Stop 
“r” 
…Reverse 
− 
− 
D004 
Process variable (PV), 
PID feedback monitor 
Displays the scaled PID process 
variable (feedback) value (A075 is 
scale factor), 
0.00 to 10000 
− 
% times 
constant 
D005 
Intelligent input 
terminal status 
Displays the state of the intelligent 
input terminals: 
 
 
 
 
 
 
− 
− 
ON
OFF 
 7 
3 2 1 
Terminal numbers