Analog Output Operation
 
In inverter applications it is useful to monitor the 
inverter operation from a remote location or from the 
front panel of an inverter enclosure. In some cases, 
this requires only a panel-mounted volt meter. In other 
cases, a controller such as a PLC may provide the 
inverter’s frequency command, and require inverter 
feedback data (such as output frequency or output 
current) to confirm actual operation. The analog output 
terminal [AM] serves these purposes. 
The inverter provides an analog voltage output on terminal [AM] with terminal [L] as analog 
GND reference. The [AM] can output inverter frequency or current output value. Note that 
the voltage range is 0 to +10V (positive-going only), regardless of forward or reverse motor 
rotation. Use 
C028
 to configure terminal [AM] as indicated below. 
Func. 
Code 
Description 
00 
Inverter output frequency 
01 
Inverter output current 
02 
Inverter output torque 
03 
Digital output freqnency 
04 
Inverter output goltage 
05 
Inverter input power 
06 
Electronic Thermal Load 
07 
LAD frequency 
08 
Digital current monitor 
10 
Cooling fin temperature 
12 
General purpose 
15 
Pulse train   
C028 
16 
Option 
AM  H  O  OI  L 
+
A GND 
Analog 
Voltage 
Output 
10VDC 
full scale, 
2mA max
See I/O specs on page 21,22