Hitachi hitachi series inverter 사용자 설명서

다운로드
페이지 99
 
45 
The [AM] signal offset and gain are adjustable, as indicated below. 
Func. 
Description 
Range 
Default 
C106 
[AM] output gain 
0.~255. 
100. 
C109 
[AM] output offset 0.0~10.0 
0.0 
The graph below shows the effect of the gain and offset setting. To calibrate the [AM] 
output for your application (analog meter), follow the steps below: 
1. Run the motor at the full scale speed, or most common operating speed. 
a. If the analog meter represents output frequency, adjust offset (
C109
) first, and then 
use 
C106
 to set the voltage for full scale output. 
b. If [AM] represents motor current, adjust offset (
C109
) first, and then use 
BC106
 to set 
the voltage for full scale output. Remember to leave room at the upper end of the 
range for increased current when the motor is under heavier loads. 
 
 
 
 
 
 
 
 
 
NOTE: As mentioned above, first adjust the offset, and then adjust the gain. Otherwise the 
required performance cannot be obtained because of the parallel movement of the offset 
adjustment. 
Full scale (FS) 
Hz or A 
AM output
10V
0
1/2 FS 
5V
C106
=0~255 
AM output gain adjustment 
Full scale (FS) 
Hz or A 
AM output 
10V
0
1/2 FS 
5V
C109
=0~10 
Parallel 
movement 
AM output offset adjustment