Siemens SCALANCE X-200 사용자 설명서

다운로드
페이지 296
 
Configuration / diagnostics using remote mechanisms 
 
6.3 Configuration using Web Based Management (WBM) and Command Line Interface (CLI) 
SCALANCE X-200 
Operating Instructions, 12/2011, A5E00349864-19 
241
 
 
Variable 
Access rights 
Description 
snX200FaultState 
Read and write 
Displays the error status of the device. Possible values: 
 
1 No error 
 
2 Error 
snX200FaultValue 
Read only 
Errors are assigned an ascending index according to the order in 
which they occur. This 4-byte variable specifies the index. 
snX200RmState 
Read only 
Indicates whether the redundancy manager is active or passive. 
Possible values: 
 
1 The redundancy manager is passive. The IE Switch X-200 is 
operating as redundancy manager and has opened the ring. In 
other words, the bus with the IE Switches X-200 connected to it is 
operating correctly. The "Passive" status is also shown when the 
redundancy manager mode is disabled. 
 
2 The redundancy manager is active. The IE Switch X-200 is 
operating as redundancy manager and has closed the ring. In 
other words, the bus with the IE Switches X-200 connected to it is 
interrupted (fault). The redundancy manager switches through the 
connection between the ring ports and thus restores a functioning 
bus configuration. 
snX200RmStateChanges 
Read only 
Indicates how often the redundancy manager was switched to 
"active". 
snBootStrapVersion 
Read only 
The firmware version of the bootloader in the format major.minor. 
snHwVersion 
Read only 
The hardware version of the system in the format major.minor. 
snInfoSerialNr 
Read only 
The serial number of the product. 
snMacAddressBase 
Read only 
The MAC address of the IE Switch X-200. 
snSwVersion 
Read only 
The software version of the system. 
snInfoMLFB 
Read only 
The MLFB number of the device. 
snX200PowerSupplyState 
Read only 
State of the redundant power supply: 
1 Redundant supply  
2 No redundant supply 
Note:  
The following devices do not have a redundant power supply: 
- SCALANCE X204 IRT PRO 
- SCALANCE X202-2P IRT 
- SCALANCE X201-3P IRT 
- SCALANCE X201-3P IRT PRO 
SnX200RmMode 
Read only 
The redundancy manager mode 
1 The IE Switch X-200 is redundancy manager. 
2 The IE Switch X-200 is not redundancy manager.