Siemens DataNET Hub (DNH) 사용자 설명서

다운로드
페이지 97
 
2000585-001 
Data Communications Setup  
••••  63 
System Status LEDs, 
Continued
 
 
The yellow (WARN) blink codes are shown below. The yellow (WARN) 
status LED will light any time a link error is present. That is, any time at 
least one red (FAULT) link LED is lit, the yellow status LED will also be lit 
(green and red LEDs will be off). 
Number of blinks
Error: 
1 RAM 
failure 
FLASH checksum error 
3 Invalid 
configuration 
4 Reserved 
Other hardware failure during self-test 
Duplicate IP address detected 
7 Cross-link 
failure 
 
The Uplink and Downlink ports each have a status LED. The LED for 
each port can either indicate red (FAULT) or green (NORMAL). 
The green LED is on once the link has become established (active). It 
will remain on as long as the link is active (i.e., polls/responses are re-
ceived within a timeout period). The green LED will blink off (~100mSec) 
for each information-carrying frame sent or received, with a minimum of 
100mSec “on” time between blinks. 
When the hub detects an address loop (the same IP address is being 
used on multiple hubs), the port is disabled and green LED will remain 
off until the user changes the IP addresses and resets the port. 
On active links, the hub indicates transient errors by blinking the red LED 
briefly (~100mSec). The red LED is on if the link has been active since 
the hub was last powered on or reset but has subsequently become in-
active. A link will become inactive if the wires are disconnected, shorted, 
or a message is dropped after three retries. If a channel has never been 
active since the DNH was last powered-up or reset, both LEDs will be 
off. This is intended to reduce spurious error indications for channels that 
are completely disconnected. 
Yellow (WARN) LED 
Blink Codes  
Hub Port LEDs 
Green (NORMAL) LED 
Red (FAULT) LED