••••  Data Communications Setup 
2000585-001 
Troubleshooting, 
Continued
 
 
The device may have an invalid or duplicate device ID, IP address, Sub-
net mask, or iproute. 
Verify the configuration parameters by connecting a PC serial port to the 
Configuration Port, logging in, and typing config display
> login password 
Applied Automation 
Advance DataNET Hub  
local> config display 
Config: 
type            DATANET HUB 
address ip          172.16.99.7 
subnetmask        255.255.0.0 
address ethernet 00.c0.c9.01.20.a7 
device ID           172.16.99.7 
1       time server ip     0.0.0.0 

Make sure each Hub half has a unique IP address and that both Hub 
halves have the same device ID. Usually the device ID is set to the IP 
address of the ‘A’ Hub. 
Advance Network devices periodically broadcast their status for diagnos-
tic and network routing purposes. 
The Subnet mask must be identical on all Advance network devices 
(Maxum analyzer, NAU, ANCB, DNH), and connected to a single net-
work, for the broadcast message to be received properly. If a remote de-
vice does not show up in the device routing table, verify that the remote 
device matches the local device Subnet mask. 
Configuration Parameter 
Errors: