Siemens M200D 사용자 설명서

다운로드
페이지 114
 
Diagnostics 
 
7.2 Diagnostics with LED 
M200D AS-Interface Basic 
Manual, 03/2009, A5E01668085-01 
81
 
AS-i / fault LED (possible colors: red / green / OFF)   
 
Status 
Meaning 
Cause 
OFF 
Device not ready 
• 
No power supply for electronics 
• 
Hardware fault in AS-i slave 
Green 
Device ready 
Communication active, normal operation 
Flashing red/yellow   Slave address = 0 
— 
Flashing red/green  I/O fault 
S1 bit set  
Flashing red 
Serious I/O fault 
• 
Hardware fault in AS-i slave 
Red 
No data exchange 
• 
Master in stop mode 
• 
Slave not entered in LPS 
• 
Slave has wrong IO/ID code 
• 
Slave in reset mode 
STATE LED (possible colors: red / green / yellow / OFF)   
 
Status 
Meaning 
Cause 
OFF 
No activation 
Contact block OFF 
Green 
Activation 
Contact block ON 
by means of controller or hand-held device 
Flickering green  
Manual local control mode
control by input 
Contact block ON 
by input action 
Flashing yellow 
Mode fault 
Contact block OFF 
manual mode connection interruption without 
reset to automatic mode 
Flickering yellow 
Manual local control mode
control by input 
Contact block OFF 
by input control function  
(e.g. quick stop) 
Red 
Contact block defective 
Switching status ≠ switching command 
PWR LED (possible colors: green / OFF)   
 
Status 
Meaning 
Cause 
OFF 
No U
AS-i
 
No AS-i voltage 
Green 
U
AS-i
 present 
AS-i voltage present 
PWR AUX LED (possible colors: green / OFF)   
 
Status 
Meaning 
Cause 
OFF 
No U
AUX
 
No auxiliary voltage 
Green 
U
AUX
 present 
Auxiliary voltage present