Diagnostics 
 
7.2 Diagnostics with LED 
M200D AS-Interface Basic 
Manual, 03/2009, A5E01668085-01 
83
 
 
SF LED  STATE LED 
DEVICE LED 
Device faults 
Red 
Red 
Red 
Current flowing with no ON command 
(e.g.: contact welded, thyristor failure) 
Red 
OFF 
Red 
Electronics defective, self-test fault 
Red 
OFF 
OFF 
No connection with AS-i 
 
System fault/alarm    
 
SF LED  STATE LED 
DEVICE LED 
System fault/alarm 
Red 
OFF 
Yellow 
• 
Current not flowing despite ON command 
(residual current detected) 
• 
Internal trip 
–  Connector monitoring 
–  Circuit breaker tripped / shut down 
• 
No contact block supply voltage 
• 
External encoder supply short-circuit 
OFF 
Green 
(when contact 
block is ON) 
Flashing yellow  Group alarm due to: 
• 
Thermal motor model overload 
• 
Temperature sensor overload 
• 
Asymmetry 
• 
Incorrect parameter value 
OFF 
OFF 
OFF 
No supply voltage for electronics 
 
Group fault   
 
SF LED  STATE LED 
DEVICE LED 
Group fault 
Red 
OFF 
OFF 
Device diagnosis available