Diagnostics 
 
7.2 Diagnostics with LED 
 
M200D AS-Interface Basic 
82
 
Manual, 03/2009, A5E01668085-01 
Input LEDs IN1 ... IN4 (possible colors: green / OFF)  
 
Status 
Meaning 
Cause 
OFF 
No 24 V DC 
No input signal 
Green 
24 V DC present 
Input signal present 
Output LED OUT1 (possible colors: green / OFF) 
 
Status 
Meaning 
Cause 
OFF 
No 24 V DC 
No output signal 
Green 
24 V DC present 
Output signal present 
7.2.2 
LED display combinations 
You can define certain faults more accurately by looking at the combination of indicator 
statuses.   
Device status / operating mode    
 
SF LED  STATE LED 
DEVICE LED 
Device status / operating mode 
OFF 
Green 
Green 
Motor ON; no fault 
OFF 
OFF 
Green 
Motor OFF; no fault 
OFF 
Flashing yellow  Green 
Manual mode connection interruption without reset 
to automatic mode 
OFF 
Flickering yellow  Green 
Shutdown by input control function  
(e.g. quick stop) 
OFF 
OFF 
Flashing green 
Device not initialized in factory or no startup 
parameters received (parameter bits from master) 
 
Device faults   
 
 
Note 
Acknowledging device faults 
A device fault can only be acknowledged by switching the power off and then on again. 
If the fault occurs again, however, the motor starter must be replaced.