Diagnostics 
 
7.3 Diagnostics via parameter channel (parameter echo) 
 
M200D AS-Interface Basic 
84
 
Manual, 03/2009, A5E01668085-01 
7.3 
Diagnostics via parameter channel (parameter echo) 
Diagnostics (diagnostic message and diagnostic read procedure)      
In the PLC, you can tell whether a fault has occurred by looking at the "I/O fault bit" (S1) on 
the slave status tab page. The AS-i master enters the S1 value in the list of I/O faults (LPF) 
that have been signaled. The PLC can read this list via the "GET_LPF" command and then 
signal a specific diagnostic value from the slave.   
 
Slave diagnostics echo (parameter echo) 
Bit P0 defines whether a fault diagnosis (P0 = 1) or alarm/message diagnosis (P0 = 0) is 
returned to the master as a slave response. 
The parameter value (P0 = (0 / 1); P1 = x; P2 = x; P3 = x) is sent to the master via the 
"Write_Parameter" command. 
 
 
 
Note 
In the parameter echo, only one fault or message is output at any one time; this is always the 
one with the highest priority. No further messages/faults can be output while this 
message/fault is present. 
 
 
 
Call (master to slave): 
P3 
P2 
P1 
P0 
A/B 
x (free) 
x (free) 
 
Feedback (slave to master): 
Parameter echo – alarms (A) / messages (M) 
P3 
P2 
P1 
P0 
Decimal  Message / alarm 
00 
No alarm / message 
04 
(M) Thermal motor model deactivated 
10 
(M) Manual local control 
11 
(A) Prewarning limit of motor model exceeded 
12 
(M) Temperature sensor deactivated