Vermont Casting DVT38IN 사용자 설명서

다운로드
페이지 48
6
Chateau™
20011956
A) Flat on wall  
B) Cross corner 
C)  **Island
D) *Room divider  E) *Flat on wall corner 
F)  Chase installation
Y) 6” minimum
NOTE (Fig. 3):  
** Island (C) and Room Divider (D) installation is possible as long as 
the horizontal portion of the vent system (X) does not exceed 20’ (6 
m).  See details in Venting Section.
*  When you install your gas fireplace in (D) Room divider or (E) Flat 
on wall corner positions (Y), a minimum of 6” (152 mm) clearance 
must be maintained from the perpendicular wall and the front side 
edge of the fireplace.
Appliance
  Top Standoffs ..................................................... 0” (0 mm)
  Bottom* .............................................................. 0” (0 mm)
  Side Standoffs .................................................... 0” (0 mm)
  Back Standoffs ................................................... 0” (0 mm)
  Front............................................................. 36” (914 mm)
  Top of Unit to Ceiling .................................... 36” (914 mm)
Venting
  Horizontal Termination through-a-side wall:
    Vertical Sections:
      Sides ...................................................... 2¹⁄₂” (64 mm)
    Horizontal Sections:
      Top ......................................................... 3¹⁄₂” (89 mm)
      Bottom ................................................... 1¹⁄₂” (38 mm)
      Sides ...................................................... 2¹⁄₂” (64 mm)
  Vertical Vent Application:
      Sides  ..................................................... 1¹⁄₂” (38 mm)
* To prevent the potential for odors, do not use epoxy-filled 
particle board directly under this fireplace.
Mantels
The height that a combustible mantel is fitted above the 
fireplace is dependent on the depth of the mantel. This 
also applies to the distance between the mantel leg (if 
fitted) and the fireplace.
For the correct mounting height and widths refer to 
Figs. 4a and 4b, the following Mantel Charts.
Noncombustible mantels and legs may be installed at 
any height and width around the appliance. 
When using paint or lacquer to finish the mantel, such 
paint or lacquer must be heat resistant to prevent 
discoloration.
Clearance to Combustibles
Y
E
A
B
C
D
F
Y
B
X
LU584-1
Locating unit
2/4/99   djt
Locating Your Fireplace
Fig. 3  Locate gas fireplace.
LU584-1
Fig. 4a  Combustible mantel minimum installation.
A
B C D E
V
W
X
Y
Z
CFM146c
DVT44
mantal chart
Mantel Chart
 
 
Mantel Shelf 
 
Mantel from Top
  Ref.  or Breast Plate  Ref.  of Comb. Chamber 
 
 
Depth
 
10” (254 mm) 
10” (254 mm)
 
9” (229 mm) 
9” (229 mm)
 
8” (203 mm) 
8” (203 mm)
 
7” (178 mm) 
7” (178 mm)
 
6” (152 mm) 
6” (152 mm)
CFM146c
Combustible 
Framing and  Fin-
ish Wall Above 
Standoffs
Standoff
Top of Sheet 
Metal
Noncombustible Fin-
ish Material
(Such as Dura Rock)
Fireplace Front
May use combus-
tible facing mate-
rial in this area
J
F
G
H
I
CFM164b
Mantel Leg Char
DVT44
4/9/03   djt
Mantel 
Leg
CFM164b
CFM170
DV Builder Front 
View
O
N
M
L
K
CFM170a
Fig. 4b   Combustible mantel leg minimum installation.
 
 
Mantel 
 
Mantel Leg from Side
  Ref. 
Leg Depth 
Ref. 
of Comb. Opening
 
12”  (305 mm) 
12”  (305 mm)
 
9”  (229 mm) 
9”  (229 mm)
 
6”  (152 mm) 
6”  (152 mm)
 
4”  (102 mm) 
4”  (102 mm)
 
3”  (76 mm) 
3”  (76 mm)
Side of Fireplace
Noncombustible 
Finish Material