Gas Inlet and Manifold Pressures
   
Natural  LP (Propane)
  Minimum Inlet Pressure 
5.5” w.c. 
11.0” w.c.
  Maximum Inlet Pressure  14.0” w.c. 
14.0” w.c.
  Manifold Pressure 
3.5” w.c. 
10.0” w.c.
High Elevations
Input ratings are shown in BTU per hour and are 
certified without deration for elevations up to 
4,500 feet (1,370 m) above sea level.
For elevations above 4,500 feet (1,370 m) in USA, 
installations must be in accordance with the 
current ANSI Z223.1/NFPA 54 and/or local codes 
having jurisdiction.
In Canada, please consult provincial and/or local 
authorities having jurisdiction for installations at 
elevations above 4,500 feet (1,370 m).
WARNING:  Improper installation, adjust-
ment, alteration, service or maintenance 
can cause injury or property damage. Refer 
to this manual for correct installation and 
operational procedures. For assistance or 
additional information consult a qualified 
installer, service agency, or the gas supplier.
Gas Line Installation
FP297A
INSTA VENT FREE
UVHB26 GAS SUPPLY 
7/1/98
FP297A
1/2” Gas Supply
1/2” NPT X 1/2” Flare 
Shut-off Valve
1/2” Gas Tight or 
Tinned Copper 
(from valve)
(Not provided)
Fig. 7  Typical gas supply installation.
When purging gas line the front glass must 
be removed.
A gas shut off valve must be installed on 
the gas pipe line going into the appliance 
within easy access. Refer to local codes.
The gas pipeline can be brought in through the top of 
the valve box assembly.    
The gas line connection can be made with properly 
tinned 1/2” copper tubing or 1/2” gas tight.  Some 
municipalities have additional local codes, it is always 
best to consult your local authority and the CSA-B149.1 
installation codes.
For USA installations consult the current National Fuel 
Gas Code, ANSI Z223.1/NFPA 54.
Always check for gas leaks with a mild 
soap and water solution applied with a 
brush no larger than 1” (25 mm). Never 
apply soap and water solution with a spray 
bottle. Do not use an open flame for leak 
testing.
The fireplace valve must not be subjected 
to any test pressures exceeding 1/2 psi. 
Isolate or disconnect this or any other gas 
appliance control from the gas line when 
pressure testing.
The fireplace is equipped with an inlet and manifold 
pressure test point, therefore it is not necessary to pro-
vide a 1/8” test point up stream of the control.
When using copper, use only approved fittings. Always 
provide a union
 when using black iron pipe so the gas 
line can be easily disconnected for burner servicing. A 
union may not be behind a wall. Refer to the gas speci-
fications for pressure details and ratings.
Gas Specifications
 
 
 
 
Max. 
Min.
 
  
 
Gas 
 Input 
 Input
  Model 
Fuel 
Control 
BTU/hr  BTU/hr
  DVT38IN  Natural Gas  American Flame  46,000  32,000
  DVT38IP 
Propane 
AF-4034 
46,000  36,000
  DVT44IN  Natural Gas 
with 
60,000  37,000
  DVT44IP 
Propane 
7.5V DC Hi/Lo  60,000  45,000
The fireplace, when installed, must be elec-
trically connected and grounded in accord-
ance with local codes or, in the absence 
of local codes, with the current CSA C22.1 
Canadian Electrical Code or the national 
electrical code  ANSI/NFPA No. 70 in the 
USA.
It is strongly suggested that the wiring of 
the Electrical Junction Box be carried out 
by a licensed electrician. 
Ensure the power to the supply line has 
been disconnected before commencing 
this procedure.                
Electrical Junction Box