Indoor & Outdoor Split 
Geothermal Comfort Systems
Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05
47
Equipment Selection 
Table 1b: Selection of Coils other than Above Models for Puron® Geothermal Split 
Systems
Model*
Nominal 
Tons*
Evaporator 
Temp (ºF)
CFM
Capacity
(MBtuh)**
Add-on CK5P 
Coil with TXV
AND Vspd 
furn.
FX4 PSC 
Fan Coil
(not an ARI rated 
combination)
026 - Part Load
1.5
50
530
19.2 - 22.4
A/T/W 036
018
026 - Full Load
2.0
52
880
24.2 - 28.2
A/T/W 036
030
038 - Part Load
2.5
51
700
25.2 - 29.2
A/T/W 048
036
038 - Full Load
3.0
50
1200
34.5 - 40.1
A/T 060
036
049 - Part Load
3.5
47
1000
34.3 - 39.9
A/T 060
042
049 - Full Load
4.0
48
1650
46.3 - 53.8
X060
048
064 - Full Load
5.0
48
1850
54.5 - 63.3
2 - A/T/W 036
060
*  Nominal tons are at ARI/ISO 13256-1 GLHP conditions.  Two-stage units may be operated in single-stage mode if desired, 
where smaller capacity is required.  For example, a model 026 may be used as a 1-1/2 ton unit if “locked” into 1st stage 
operation only.  If PSC fan is used, unit must be “locked” into either 1st or 2nd stage.  An ECM fan is required for two-stage 
operation and for ARI ratings.  Size air handler for “Full Load” if operating in two-stage mode.
**When selecting an air handler based upon the above conditions, choose entering WB temperature of 67ºF. Use evaporator 
temperature, CFM and capacity requirements as listed above. The air handler capacity must be at least at the minimum 
capacity shown in the table in order for the ARI rating condition to be valid. See Figure 1 for an example selection.
Indoor Coil Selection - R-22 Units
Geothermal split system heat pumps with R-22 
refrigerant are rated in the ARI directory with a 
“generic” indoor coil match and PSC fan.  Selection of 
air handlers that attain the published ARI ratings must 
meet or exceed the specifi cations listed in Table 2.  
TXV is required. 
 Cap tubes and fi xed orifi ces are 
not acceptable.  
Table 2: R-22 Air Handler Characteristics
Model*
Nominal 
Tons*
Evaporator 
Temp (ºF)
CFM
Capacity
(MBtuh)**
018
1.5
50
600
18.5 - 21.3
024
2.0
47
800
25.5 - 29.3
030
2.5
49
1000
31.5 - 36.2
036
3.0
48
1200
37.0 - 42.5
042
3.5
45
1400
42.2 - 48.5
048
4.0
46
1600
50.0 - 57.5
060
5.0
45
2000
58.0 - 66.7
*  Nominal tons are at ARI/ISO 13256-1 GLHP conditions.
**When selecting an air handler based upon the above conditions, choose entering WB temperature of 67ºF. Use evaporator 
temperature, CFM and capacity requirements as listed above. The air handler capacity must be at least at the minimum 
capacity shown in the table in order for the ARI rating condition to be valid. See Figure 1 for an example selection.
GT-PX Air Handler Characteristics for Brands other than Above Models
R-22 Air Handler Characteristics