Two-Stage Indoor Split 
Puron
®
 Systems
49
Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05
GT-PX Split (50YDS) Series
General
The liquid source heating/cooling split condensing 
units shall be ARI/ISO/ASHRAE 13256-1 (ground-
source closed-loop) performance certifi ed and listed 
by a nationally recognized safety-testing laboratory or 
agency, such as the Canadian Standards Association 
(CSA US). Each unit shall be water run-tested at the 
factory. Each unit shall be pallet mounted and shipped 
with appropriate protective packaging to help avoid 
damage in transportation. The units shall be warranted 
by the manufacturer against defects in materials and 
workmanship for a period of fi ve years on all parts, and 
ten years on the compressor and refrigerant circuit 
parts with a service labor allowance during the fi rst 30 
days. An optional extended warranty is available for the 
GT-PX Series units, which adds a labor allowance and 
trip charge. The water source units shall be designed to 
operate with entering fl uid temperature between 20°F 
and 120°F.
Casing & Cabinet
The cabinet shall be fabricated from heavy-gauge 
galvanized steel and painted with an epoxy powder 
coating. The interior shall be insulated with 1/2” thick, 
multi-density, coated glass fi ber. Three compressor 
compartment access panels shall be provided and shall 
be removable with linesets and water piping in place. The 
internal component layout shall provide for major service 
with the unit in-place for restricted access installations.
Refrigerant Circuit
All units shall contain Puron
®
 (HFC 410A) sealed 
refrigerant circuit employing a hermetic motor 
compressor, bidirectional thermal expansion valve, 
reversing valve, coaxial tube water-to-refrigerant heat 
exchanger and service ports. An optional Hot Water 
Generator (desuperheater) coil shall be provided. 
Compressors shall be Copeland UltraTech™ Two-
Stage scroll type designed for heat pump duty and 
mounted on spring vibration isolators. Compressor 
motors shall be single phase PSC with internal over 
load protection. A factory provided bidirectional fi lter 
drier shall be included in all models. The coaxial water-
to-refrigerant heat exchangers shall be designed for 
close approach temperatures and be construct ed of 
a convoluted copper (optional cupronickel) inner tube 
and a steel outer tube. The thermal expansion valve 
shall provide proper superheat over the entire fl uid 
temperature range with minimal “hunting”. The valve 
shall operate only in the heating mode with the use of 
an internal check valve. The water-to-refrigerant heat 
exchanger, optional desuperheater coil and refrigerant 
suction lines shall be insulated to prevent condensation 
at low liquid temperatures.
Electrical
CXM Control - A microprocessor-based compressor 
controller shall be provided to monitor and control 
unit operation. The control shall provide compressor 
sequencing, high and low pressure monitoring, fi eld 
selectable low water temperature sensing, over/under 
voltage monitoring, and unit performance sentinel 
(UPS). The control shall also provide for water valve 
connection, a test mode, short cycle protection, random 
start-up, as well as fault LED, fault memory, and 
intelligent fault retry.
The control shall employ quick attach harness 
assemblies for low voltage connections to the control 
board to aid in troubleshooting or replacement. An 
integral terminal block with screw terminals shall be 
provided on the control for fi eld low voltage connections. 
A circuit breaker protected 75VA transformer shall be 
employed. Line voltage box lugs shall be provided for 
unit wiring. Units shall have knockouts for entrance of 
low and line voltage wiring. The control box shall be 
harness plug-connected for easy removal. Residential 
models shall have a dual circut-breaker protected power 
block for the connection of external Flow Controller 
pump module.
Piping
Supply and return water connections, as well as Hot 
Water Generator (desuperheater) connections shall be 
1” FPT brass swivel fi ttings which provide a union and 
eliminate the need for pipe wrenches and sealants when 
making fi eld connections. A thread by sweat fi tting shall 
be provided for connection to the water heater. All water 
piping shall be insulated to prevent condensation at low 
liquid temperatures.